Частотный преобразователь allen bradley инструкция на русском

Allen-Bradley PowerFlex 4M User Manual

  • Contents

  • Table of Contents

  • Troubleshooting

  • Bookmarks

Quick Links

Adjustable

Frequency AC

Drive

FRN 1.xx — 2.xx

User Manual

www.abpowerflex.com

loading

Related Manuals for Allen-Bradley PowerFlex 4M

Summary of Contents for Allen-Bradley PowerFlex 4M

  • Page 1
    Adjustable Frequency AC Drive FRN 1.xx — 2.xx User Manual www.abpowerflex.com…
  • Page 2
    Allen-Bradley, Rockwell Automation, and PowerFlex are registered trademarks of Rockwell Automation, Inc. DriveExplorer, DriveExecutive, and SCANport are trademarks of Rockwell Automation, Inc. PLC is a registered trademark of Rockwell Automation, Inc. PowerFlex 4M Adjustable Frequency Drive FRN 1.xx — 2.xx User Manual…
  • Page 3
    Description for bits 6, 7, and 15 of register address 8192 updated. Information on reading register address 8193 clarified. Figure C.1, Network Wiring Diagram, updated. Guidelines on standard RS485 wiring practices added. PowerFlex 4M Adjustable Frequency Drive FRN 1.xx — 2.xx User Manual Publication 22F-UM001D-EN-E…
  • Page 4
    Description for option 21 of parameter t221 [Relay Out Sel] corrected. 3-15 Invalid catalog number for L Type Filter deleted. B-4, B-10 Graphic for the “Connecting an RS-485 Network” section corrected PowerFlex 4M Adjustable Frequency Drive FRN 1.xx — 2.xx User Manual Publication 22F-UM001D-EN-E…
  • Page 5: Table Of Contents

    Product Selection ….B-1 Product Dimensions ….B-6 PowerFlex 4M Adjustable Frequency Drive FRN 1.xx — 2.xx User Manual Publication 22F-UM001D-EN-E…

  • Page 6
    DSI Cable Accessories ….D-2 Connecting an RS-485 Network ..D-3 Index PowerFlex 4M Adjustable Frequency Drive FRN 1.xx — 2.xx User Manual Publication 22F-UM001D-EN-E…
  • Page 7: Who Should Use This Manual

    Safety Guidelines for the SGI-1.1 www.rockwellautomation.com/ Application, Installation and literature Maintenance of Solid State Control A Global Reference Guide for 0100-2.10 Reading Schematic Diagrams Guarding Against Electrostatic 8000-4.5.2 Damage PowerFlex 4M Adjustable Frequency Drive FRN 1.xx — 2.xx User Manual Publication 22F-UM001D-EN-E…

  • Page 8: Manual Conventions

    Overview Manual Conventions • In this manual we refer to the PowerFlex 4M Adjustable Frequency AC Drive as: drive, PowerFlex 4M or PowerFlex 4M Drive. • Parameter numbers and names are shown in this format: P101 [Motor NP Volts] Name…

  • Page 9: General Precautions

    1 minute. If this condition is unacceptable, the bus regulator must be disabled (see parameter A441). In addition, installing a properly sized dynamic brake resistor will provide equal or better performance in most cases. PowerFlex 4M Adjustable Frequency Drive FRN 1.xx — 2.xx User Manual Publication 22F-UM001D-EN-E…

  • Page 10: Catalog Number Explanation

    17.5 3.7 (5.0) 18.0 7.5 (10.0) 25.0 5.5 (7.5) 24.0 10.0 (15.0) 33.0 7.5 (10.0) Additional accessories, options and adapters are available. See Appendix B for details. PowerFlex 4M Adjustable Frequency Drive FRN 1.xx — 2.xx User Manual Publication 22F-UM001D-EN-E…

  • Page 11: Installation/Wiring

    Opening the Cover 1. Press and hold in the tabs on each side of the cover. 2. Pull the cover out and up to release. PowerFlex 4M Adjustable Frequency Drive FRN 1.xx — 2.xx User Manual Publication 22F-UM001D-EN-E…

  • Page 12: Mounting Considerations

    Horizontal Clearance between drives Minimum Maximum 0 mm and greater -10°C (14°F) 40°C (104°F) 25 mm and greater -10°C (14°F) 50°C (122°F) Drive enclosure is rated IP20, NEMA/UL Type Open. PowerFlex 4M Adjustable Frequency Drive FRN 1.xx — 2.xx User Manual Publication 22F-UM001D-EN-E…

  • Page 13: Ac Supply Source Considerations

    2. Pull the jumper completely out of the drive chassis. 3. Tighten the screw to keep it in place. Figure 1.1 Jumper Location (Frame A shown) Important: Tighten screw after jumper removal. PowerFlex 4M Adjustable Frequency Drive FRN 1.xx — 2.xx User Manual Publication 22F-UM001D-EN-E…

  • Page 14
    Phase to ground voltage exceeds 125% of normal • or Install Isolation Transformer line to line voltage with grounded secondary if Ungrounded distribution system necessary. Appendix B Refer to for accessory ordering information. PowerFlex 4M Adjustable Frequency Drive FRN 1.xx — 2.xx User Manual Publication 22F-UM001D-EN-E…
  • Page 15: General Grounding Requirements

    Grounding points must comply with national and local industrial safety regulations and/or electrical codes. Motor Ground The motor ground must be connected to one of the ground terminals on the drive. PowerFlex 4M Adjustable Frequency Drive FRN 1.xx — 2.xx User Manual Publication 22F-UM001D-EN-E…

  • Page 16
    Some local codes may require redundant ground connections. The integrity of all connections should be periodically checked. PowerFlex 4M Adjustable Frequency Drive FRN 1.xx — 2.xx User Manual Publication 22F-UM001D-EN-E…
  • Page 17: Fuses And Circuit Breakers

    Fusing The PowerFlex 4M has been UL tested and approved for use with input fuses. The ratings in the table that follows are the maximum recommended values for use with each drive rating. The devices listed in this table are provided to serve as a guide.

  • Page 18
    When using a Manual Self-Protected (Type E) Combination Motor Controller, the drive must be installed in a ventilated or non-ventilated enclosure with the minimum volume specified in this column. Application specific thermal considerations may require a larger enclosure. PowerFlex 4M Adjustable Frequency Drive FRN 1.xx — 2.xx User Manual Publication 22F-UM001D-EN-E…
  • Page 19: Power Wiring

    Do not use THHN or similarly coated wire in wet areas. Any wire chosen must have a minimum insulation thickness of 15 mils and should not have large variations in insulation concentricity. PowerFlex 4M Adjustable Frequency Drive FRN 1.xx — 2.xx User Manual Publication 22F-UM001D-EN-E…

  • Page 20
    If it is necessary to disconnect power to the motor with the drive outputting power, an auxiliary contact should be used to simultaneously disable drive control run commands. PowerFlex 4M Adjustable Frequency Drive FRN 1.xx — 2.xx User Manual Publication 22F-UM001D-EN-E…
  • Page 21
    Drive will not power up without a jumper or inductor connected. U/T1 To Motor U/T1 Switch any two motor leads to change forward V/T2 To Motor V/T2 direction. W/T3 To Motor W/T3 PowerFlex 4M Adjustable Frequency Drive FRN 1.xx — 2.xx User Manual Publication 22F-UM001D-EN-E…
  • Page 22
    When the AC line is removed, there will be a loss of any inherent regenerative braking effect that might be present — the motor will coast to a stop. An auxiliary braking method may be required. PowerFlex 4M Adjustable Frequency Drive FRN 1.xx — 2.xx User Manual Publication 22F-UM001D-EN-E…
  • Page 23: I/O Wiring Recommendations

    To improve noise immunity, the I/O terminal block Common must be connected to ground terminal/protective earth. If using the RS485 (DSI) port, I/O Terminal 16 should also be connected to ground terminal/protective earth. PowerFlex 4M Adjustable Frequency Drive FRN 1.xx — 2.xx User Manual Publication 22F-UM001D-EN-E…

  • Page 24
    Digital Input 2 Preset Freq Program with t202 [Digital In2 Sel]. t202 Drive supplied power for digital inputs. +24V DC – Maximum output current is 100mA. PowerFlex 4M Adjustable Frequency Drive FRN 1.xx — 2.xx User Manual Publication 22F-UM001D-EN-E…
  • Page 25
    [Digital In1 Sel] = 3 “Aux Fault” t221 [Relay Out Sel] = 10 “Above Anlg V” t222 [Relay Out Level] = % Voltage Trip PTC (hot) × 100 Trip PTC (hot) PowerFlex 4M Adjustable Frequency Drive FRN 1.xx — 2.xx User Manual Publication 22F-UM001D-EN-E…
  • Page 26
    Each digital input draws 6 mA. closed at the same time, an undetermined state could occur. 2 Wire SNK Control — Internal Supply (SNK) Run FWD/Run REV Stop-Run Forward Stop-Run Reverse PowerFlex 4M Adjustable Frequency Drive FRN 1.xx — 2.xx User Manual Publication 22F-UM001D-EN-E…
  • Page 27
    Direction Mode]. I/O Terminal 03 +24V Common determines direction. Each digital input draws 6 mA. 3 Wire SNK Control — Internal Supply (SNK) Reversing Stop Start Direction PowerFlex 4M Adjustable Frequency Drive FRN 1.xx — 2.xx User Manual Publication 22F-UM001D-EN-E…
  • Page 28
    I/O Terminal 13 (potentiometer wiper) should be daisy-chained to each drive. All drives must be powered up for the analog signal to be read correctly. PowerFlex 4M Adjustable Frequency Drive FRN 1.xx — 2.xx User Manual Publication 22F-UM001D-EN-E…
  • Page 29: Start And Speed Reference Control

    Preset Inputs Active Start and Direction commands come from P106 [Start Source]. Run as specified by P108 [Speed Reference]. Start and Direction commands come from P106 [Start Source]. PowerFlex 4M Adjustable Frequency Drive FRN 1.xx — 2.xx User Manual Publication 22F-UM001D-EN-E…

  • Page 30
    Preset Frequency. by [Preset Freq x] See A410-A413 [Preset Freq 0-3] t201 or t202 = 4 page 3-21. P109 [Accel Time 1]/P110 [Decel Time 1] are used. PowerFlex 4M Adjustable Frequency Drive FRN 1.xx — 2.xx User Manual Publication 22F-UM001D-EN-E…
  • Page 31: Emc Instructions

    • Conformity of the drive with CE EMC requirements does not guarantee an entire machine installation complies with CE EMC requirements. Many factors can influence total machine/installation compliance. PowerFlex 4M Adjustable Frequency Drive FRN 1.xx — 2.xx User Manual Publication 22F-UM001D-EN-E…

  • Page 32
    Keep wire length as short as possible between the enclosure entry point and the EMI filter. Integral EMI filters are available on 240V, 1-Phase drives and 380V, 3-Phase drives. PowerFlex 4M Adjustable Frequency Drive FRN 1.xx — 2.xx User Manual Publication 22F-UM001D-EN-E…
  • Page 33
    Installations on a public low voltage power network may require additional external harmonic mitigation. • Other drive ratings meet the current harmonic requirements of EN61000-3-2 without additional external mitigation. PowerFlex 4M Adjustable Frequency Drive FRN 1.xx — 2.xx User Manual Publication 22F-UM001D-EN-E…
  • Page 34
    1-24 Installation/Wiring Notes: PowerFlex 4M Adjustable Frequency Drive FRN 1.xx — 2.xx User Manual Publication 22F-UM001D-EN-E…
  • Page 35: Prepare For Drive Start-Up

    Chapter Start Up This chapter describes how to start up the PowerFlex 4M Drive. To simplify drive setup, the most commonly programmed parameters are organized in a single Basic Program Group. Important: Read the General Precautions section before proceeding. ATTENTION: Power must be applied to the drive to perform the following start-up procedures.

  • Page 36
    Variable Torque Fan/Pump Applications For improved motor tuning performance when using a premium efficient motor on a variable torque load, set A453 [Boost Select] to option 2 “35.0, VT”. PowerFlex 4M Adjustable Frequency Drive FRN 1.xx — 2.xx User Manual Publication 22F-UM001D-EN-E…
  • Page 37: Integral Keypad

    Scroll through groups and parameters. Increase/decrease the value of a flashing digit. Down Arrow Enter Advance one step in programming menu. Save a change to a parameter value. PowerFlex 4M Adjustable Frequency Drive FRN 1.xx — 2.xx User Manual Publication 22F-UM001D-EN-E…

  • Page 38: Viewing And Editing Parameters

    HERTZ that group will flash. PROGRAM FAULT 5. Press the Up Arrow or Down Arrow to scroll through the parameters in the group. PowerFlex 4M Adjustable Frequency Drive FRN 1.xx — 2.xx User Manual Publication 22F-UM001D-EN-E…

  • Page 39
    [Output Frequency] is displayed. Press Enter or Sel to enter the group menu again. The Basic Program Group (page 3-8) contains the most commonly changed parameters. PowerFlex 4M Adjustable Frequency Drive FRN 1.xx — 2.xx User Manual Publication 22F-UM001D-EN-E…
  • Page 40
    Start Up Notes: PowerFlex 4M Adjustable Frequency Drive FRN 1.xx — 2.xx User Manual Publication 22F-UM001D-EN-E…
  • Page 41: Programming And Parameters

    = Stop drive before changing this parameter. = 32 bit parameter. Parameters marked 32 bit will have two parameter numbers when using RS485 communications and programming software. PowerFlex 4M Adjustable Frequency Drive FRN 1.xx — 2.xx User Manual Publication 22F-UM001D-EN-E…

  • Page 42: Parameter Organization

    Maximum Voltage A457 DB Duty Cycle A428 Program Lock A458 Testpoint Sel A459 Start At PowerUp A433 Reverse Disable A434 Motor NP FLA A461 Flying Start En A435 PowerFlex 4M Adjustable Frequency Drive FRN 1.xx — 2.xx User Manual Publication 22F-UM001D-EN-E…

  • Page 43: Display Group

    0/Drive Rated Volts Display: 0.1 VAC d005 [DC Bus Voltage] Present DC bus voltage level. Values Default Read Only Min/Max: Based on Drive Rating Display: 1 VDC PowerFlex 4M Adjustable Frequency Drive FRN 1.xx — 2.xx User Manual Publication 22F-UM001D-EN-E…

  • Page 44
    [Process Factor] or by A438 [Process Time Lo] and A439 [Process Time Hi]. Output Process Process Freq Factor Display Values Default Read Only Min/Max: 0.00/9999 Display: 0.01 – 1 PowerFlex 4M Adjustable Frequency Drive FRN 1.xx — 2.xx User Manual Publication 22F-UM001D-EN-E…
  • Page 45
    When this bit is a 1 the drive can be started. When this bit is a 0 the drive will stop. Values Default Read Only Min/Max: Display: PowerFlex 4M Adjustable Frequency Drive FRN 1.xx — 2.xx User Manual Publication 22F-UM001D-EN-E…
  • Page 46
    Main Control Board software version. Values Default Read Only Min/Max: 1.00/99.99 Display: 0.01 d017 [Drive Type] Used by Rockwell Automation field service personnel. Values Default Read Only Min/Max: 1001/9999 Display: PowerFlex 4M Adjustable Frequency Drive FRN 1.xx — 2.xx User Manual Publication 22F-UM001D-EN-E…
  • Page 47
    Read Only Min/Max: 0.0/100.0% Display: 0.1% d022 [Drive Temp] Present operating temperature of the drive power section. Values Default Read Only Min/Max: 0/120 degC Display: 1 degC PowerFlex 4M Adjustable Frequency Drive FRN 1.xx — 2.xx User Manual Publication 22F-UM001D-EN-E…
  • Page 48: Basic Program Group

    A438 Stop drive before changing this parameter. Sets the highest frequency the drive will output. Values Default 60 Hz Min/Max: 0/400 Hz Display: 1 Hz PowerFlex 4M Adjustable Frequency Drive FRN 1.xx — 2.xx User Manual Publication 22F-UM001D-EN-E…

  • Page 49
    When using option 5 “Comm Port”, if the drive is using a network for control and the user’s program is maintaining a “Start” or “Jog” command without sending a “Stop command”, the drive will start automatically when power is cycled. PowerFlex 4M Adjustable Frequency Drive FRN 1.xx — 2.xx User Manual Publication 22F-UM001D-EN-E…
  • Page 50
    • Standard DC Injection Braking for value set in A424 Brake Time]. • Drive shuts off if current limit is exceeded. Stop input also clears active fault. PowerFlex 4M Adjustable Frequency Drive FRN 1.xx — 2.xx User Manual Publication 22F-UM001D-EN-E…
  • Page 51
    Values Default 10.0 Secs Min/Max: 0.0/600.0 Secs Display: 0.1 Secs P105 [Maximum Freq] Speed P109 or A401 P110 or A402 Time [Accel Time x] [Decel Time x] PowerFlex 4M Adjustable Frequency Drive FRN 1.xx — 2.xx User Manual Publication 22F-UM001D-EN-E…
  • Page 52
    Options 0 “Idle State” (Default) • After the reset function is complete, this parameter will set 1 “Reset Defaults” itself back to “0”. • Causes an F48 Params Defaulted fault. PowerFlex 4M Adjustable Frequency Drive FRN 1.xx — 2.xx User Manual Publication 22F-UM001D-EN-E…
  • Page 53: Terminal Block Group

    12 “Jog Reverse” Drive accelerates to A404 [Jog Frequency] according to A405 [Jog Accel/Decel] and ramps to stop when input becomes inactive. A valid start will override this command. PowerFlex 4M Adjustable Frequency Drive FRN 1.xx — 2.xx User Manual Publication 22F-UM001D-EN-E…

  • Page 54
    Analog inversion can be accomplished by setting this value larger than t214 [Anlg In4-20mA Hi] or by setting t201 t202 [Digital Inx Sel] to option 15 “Anlg Invert”. Values Default 0.0% Min/Max: 0.0/ 100.0% Display: 0.1% PowerFlex 4M Adjustable Frequency Drive FRN 1.xx — 2.xx User Manual Publication 22F-UM001D-EN-E…
  • Page 55
    Enables the output to be controlled by bit 6 of the logic command word. See Writing (06) Logic Command Data on page C-4 for more information. 14-22 Reserved PowerFlex 4M Adjustable Frequency Drive FRN 1.xx — 2.xx User Manual Publication 22F-UM001D-EN-E…
  • Page 56
    [Relay Out Sel] is 6, 7, 8, 10 or 11. t221 Setting t222 Min/Max 0/400 Hz 0/180% 0/815 Volts 0/100% Values Default Min/Max: As above Display: PowerFlex 4M Adjustable Frequency Drive FRN 1.xx — 2.xx User Manual Publication 22F-UM001D-EN-E…
  • Page 57: Communications Group

    Stops drive via coast to stop. 2 “Stop” Stops drive via P107 [Stop Mode] setting. 3 “Continu Last” Drive continues operating at communication commanded speed saved in RAM. PowerFlex 4M Adjustable Frequency Drive FRN 1.xx — 2.xx User Manual Publication 22F-UM001D-EN-E…

  • Page 58
    Do not create a program that frequently uses configurable outputs to write parameter data to NVS unless C307 [Comm Write Mode] is set to option 1. PowerFlex 4M Adjustable Frequency Drive FRN 1.xx — 2.xx User Manual Publication 22F-UM001D-EN-E…
  • Page 59: Advanced Program Group

    Values Default 20.0 Secs Min/Max: 0.1/600.0 Secs Display: 0.1 Secs P105 [Maximum Freq] Speed P109 or A401 P110 or A402 Time [Accel Time x] [Decel Time x] PowerFlex 4M Adjustable Frequency Drive FRN 1.xx — 2.xx User Manual Publication 22F-UM001D-EN-E…

  • Page 60
    EEPROM memory. If the ESC key is used before the Enter key, the frequency will return to the original value following the normal accel/decel curve. Values Default 60.0 Hz Min/Max: 0.0/400.0 Hz Display: 0.1 Hz PowerFlex 4M Adjustable Frequency Drive FRN 1.xx — 2.xx User Manual Publication 22F-UM001D-EN-E…
  • Page 61
    Sets the frequency at which the drive will not operate. A setting of 0 disables this parameter. Values Default 0 Hz Min/Max: 0/400 Hz Display: 1 Hz PowerFlex 4M Adjustable Frequency Drive FRN 1.xx — 2.xx User Manual Publication 22F-UM001D-EN-E…
  • Page 62
    Sets the length of time that DC brake current is “injected” into the motor. Refer to parameter A425 Brake Level]. Values Default 0.0 Secs Min/Max: 0.0/99.9 Secs (A setting of 99.9 = Continuous) Display: 0.1 Secs PowerFlex 4M Adjustable Frequency Drive FRN 1.xx — 2.xx User Manual Publication 22F-UM001D-EN-E…
  • Page 63
    Figure B.3 on page B-7, or equivalent, must be supplied. Values Default Min/Max: Display: PowerFlex 4M Adjustable Frequency Drive FRN 1.xx — 2.xx User Manual Publication 22F-UM001D-EN-E…
  • Page 64
    1 “Rev Disabled” A435 [Flying Start En] Sets the condition that allows the drive to reconnect to a spinning motor at actual RPM. Options 0 “Disabled” (Default) 1 “Enabled” PowerFlex 4M Adjustable Frequency Drive FRN 1.xx — 2.xx User Manual Publication 22F-UM001D-EN-E…
  • Page 65
    [Maximum Freq]. When set to a value other than zero, d010 [Process Display] indicates the duration of the process. Values Default 0.00 Min/Max: 0.00/ 99.99 Display: 0.01 PowerFlex 4M Adjustable Frequency Drive FRN 1.xx — 2.xx User Manual Publication 22F-UM001D-EN-E…
  • Page 66
    2 “Max Derate” No Derate Min Derate Max Derate % of P102 [Motor NP Hertz] % of P102 [Motor NP Hertz] % of P102 [Motor NP Hertz] PowerFlex 4M Adjustable Frequency Drive FRN 1.xx — 2.xx User Manual Publication 22F-UM001D-EN-E…
  • Page 67
    A448 [SW Current Trip] Related Parameter(s): P103 Enables/disables a software instantaneous (within 100 ms) current trip. Values Default 0.0 (Disabled) 0.0/(Drive Rated Amps × 2) Min/Max: Display: 0.1 Amps PowerFlex 4M Adjustable Frequency Drive FRN 1.xx — 2.xx User Manual Publication 22F-UM001D-EN-E…
  • Page 68
    Sets the time between restart attempts when A451 [Auto Rstrt Tries] is set to a value other than zero. Values Default 1.0 Secs Min/Max: 0.0/120.0 Secs Display: 0.1 Secs PowerFlex 4M Adjustable Frequency Drive FRN 1.xx — 2.xx User Manual Publication 22F-UM001D-EN-E…
  • Page 69
    9 “7.5, CT” 10 “10.0, CT” 11 “12.5, CT” 12 “15.0, CT” 13 “17.5, CT” 14 “20.0, CT” 1/2 [Motor NP Volts] Settings 5-14 % P102 [Motor NP Hertz] PowerFlex 4M Adjustable Frequency Drive FRN 1.xx — 2.xx User Manual Publication 22F-UM001D-EN-E…
  • Page 70
    A461 [Motor NP FLA] Set to the motor nameplate rated full load amps. Values Default Drive Rated Amps 0.1/(Drive Rated Amps × 2) Min/Max: Display: 0.1 Amps PowerFlex 4M Adjustable Frequency Drive FRN 1.xx — 2.xx User Manual Publication 22F-UM001D-EN-E…
  • Page 71: Parameter Cross Reference — By Name

    Advanced Program 3-30 Motor NP Hertz P102 Basic Program Motor NP Volts P101 Basic Program Motor OL Current P103 Basic Program Motor OL Ret P111 Basic Program 3-12 PowerFlex 4M Adjustable Frequency Drive FRN 1.xx — 2.xx User Manual Publication 22F-UM001D-EN-E…

  • Page 72
    3-32 Programming and Parameters Notes: PowerFlex 4M Adjustable Frequency Drive FRN 1.xx — 2.xx User Manual Publication 22F-UM001D-EN-E…
  • Page 73: Troubleshooting

    Chapter Troubleshooting Chapter 4 provides information to guide you in troubleshooting the PowerFlex 4M drive. Included is a listing and description of drive faults (with possible solutions, when applicable). For information on… See page… For information on… See page… Drive Status…

  • Page 74
    (Type 2) that indicate possible drive component malfunction are not resettable. Caution should be used when enabling this feature, since the drive will attempt to issue its own start command based on user selected programming. PowerFlex 4M Adjustable Frequency Drive FRN 1.xx — 2.xx User Manual Publication 22F-UM001D-EN-E…
  • Page 75: Fault Descriptions

    4-1 for a description of fault types. PowerFlex 4M Adjustable Frequency Drive FRN 1.xx — 2.xx User Manual Publication 22F-UM001D-EN-E…

  • Page 76
    Failure has been detected in the 1. Cycle power. drive control and I/O section. 2. Replace drive if fault cannot be cleared. page 4-1 for a description of fault types. PowerFlex 4M Adjustable Frequency Drive FRN 1.xx — 2.xx User Manual Publication 22F-UM001D-EN-E…
  • Page 77: Common Symptoms And Corrective Actions

    [Digital Inx Select] to option 5 “Local” and activate the input. I/O Terminal 01 “Stop” input is None Wire inputs correctly and/or install not present. jumper. PowerFlex 4M Adjustable Frequency Drive FRN 1.xx — 2.xx User Manual Publication 22F-UM001D-EN-E…

  • Page 78
    [Digital Inx Select]. • Check P108 [Speed Reference] for the source of the speed reference. Reprogram as necessary. • Review the Speed Reference Control chart on page 1-19. PowerFlex 4M Adjustable Frequency Drive FRN 1.xx — 2.xx User Manual Publication 22F-UM001D-EN-E…
  • Page 79
    • Check all fuses and disconnects. Jumper between I/O Terminals None Install jumper or connect DC Bus P2 and P1 not installed and/or Inductor. DC Bus Inductor not connected. PowerFlex 4M Adjustable Frequency Drive FRN 1.xx — 2.xx User Manual Publication 22F-UM001D-EN-E…
  • Page 80
    Troubleshooting Notes: PowerFlex 4M Adjustable Frequency Drive FRN 1.xx — 2.xx User Manual Publication 22F-UM001D-EN-E…
  • Page 81: Supplemental Drive Information

    AD, BC, BD, CD, DD, ED, EFS, EF, FF, FG, GF, GG, GH. Typical designations include; Type J — JKS, LPJ, DFJ Type T — JJS, JJN Type RK1 — LPS, KTS, KTN PowerFlex 4M Adjustable Frequency Drive FRN 1.xx — 2.xx User Manual Publication 22F-UM001D-EN-E…

  • Page 82
    Manual Self-Protected (Type E) Combination Motor Controller, UL listed for 208 Wye or Delta, 240 Wye or Delta, 480Y/ 277 or 600Y/347. Not UL listed for use on 480V or 600V Delta/Delta, corner ground, or high-resistance ground systems. PowerFlex 4M Adjustable Frequency Drive FRN 1.xx — 2.xx User Manual Publication 22F-UM001D-EN-E…
  • Page 83
    Internal brake IGBT included with power ratings 5.5 kW (7.5 HP) and 7.5 kW (10.0 HP) for 240V, 3-phase drives and 5.5 kW (7.5 HP), 7.5 kW (10.0 HP) and 11.0 kW (15.0 HP) for 480V, 3-phase drives. See Appendix B for ordering information. PowerFlex 4M Adjustable Frequency Drive FRN 1.xx — 2.xx User Manual Publication 22F-UM001D-EN-E…
  • Page 84
    0.98 across entire speed range Maximum Short Circuit Rating: 100,000 Amps Symmetrical Actual Short Circuit Rating: Determined by AIC Rating of installed fuse/circuit breaker Transistor Type: Isolated Gate Bipolar (IGBT) PowerFlex 4M Adjustable Frequency Drive FRN 1.xx — 2.xx User Manual Publication 22F-UM001D-EN-E…
  • Page 85
    1.5 (2.0) 2.2 (3.0) 3.7 (5.0) 5.5 (7.5) 7.5 (10) 380–480V, 3-Phase 0.4 (0.5) 0.75 (1.0) 1.5 (2.0) 2.2 (3.0) 3.7 (5.0) 5.5 (7.5) 7.5 (10) 11 (15) PowerFlex 4M Adjustable Frequency Drive FRN 1.xx — 2.xx User Manual Publication 22F-UM001D-EN-E…
  • Page 86
    Supplemental Drive Information Notes: PowerFlex 4M Adjustable Frequency Drive FRN 1.xx — 2.xx User Manual Publication 22F-UM001D-EN-E…
  • Page 87: Accessories And Dimensions

    22F-B012N103 17.5 22F-B017N103 25.0 22F-B025N104 10.0 33.0 22F-B033N104 480V 50/60 Hz 22F-D1P5N103 3-Phase 0.75 22F-D2P5N103 22F-D4P2N103 22F-D6P0N103 22F-D8P7N103 13.0 22F-D013N104 10.0 18.0 22F-D018N104 11.0 15.0 24.0 22F-D024N104 PowerFlex 4M Adjustable Frequency Drive FRN 1.xx — 2.xx User Manual Publication 22F-UM001D-EN-E…

  • Page 88
    Alternative resistors may be used, however care must be taken when making a selection. Refer to the PowerFlex Dynamic Braking Resistor Calculator, publication PFLEX-AT001…. Requires two resistors wired in parallel. PowerFlex 4M Adjustable Frequency Drive FRN 1.xx — 2.xx User Manual Publication 22F-UM001D-EN-E…
  • Page 89
    240V 50/60 Hz 0.85 32RB001 3-Phase 10.0 40RB001 480V 50/60 Hz 3.75 18RB004 3-Phase 10.0 25RB005 11.0 15.0 2.68 32RB003 Use MTE RB Series or equivalent inductors. PowerFlex 4M Adjustable Frequency Drive FRN 1.xx — 2.xx User Manual Publication 22F-UM001D-EN-E…
  • Page 90
    This filter is suitable for use with a cable length up to 100 meters (328 feet) for Class A and 25 meters (82 feet) for Class B environments. PowerFlex 4M Adjustable Frequency Drive FRN 1.xx — 2.xx User Manual Publication 22F-UM001D-EN-E…
  • Page 91
    Compatibility: Windows 98, ME, NT 4.0 (Service Pack 3 or later), 2000 and XP See www.ab.com/drives/driveexplorer.htm for supported devices. For pricing information, refer to the PowerFlex 4-Class Price List, Publication 22-PL001…. PowerFlex 4M Adjustable Frequency Drive FRN 1.xx — 2.xx User Manual Publication 22F-UM001D-EN-E…
  • Page 92: Product Dimensions

    Accessories and Dimensions Product Dimensions Table B.I PowerFlex 4M Panel Mount Drives – Ratings are in kW and (HP) 120V AC – 1-Phase 240V AC – 1-Phase 240V AC – 3-Phase 480V AC – 3-Phase 0.2 (0.25) 0.2 (0.25) 0.2 (0.25) 0.4 (0.5)

  • Page 93
    Figure B.3 Recommended External Brake Resistor Circuitry T (L3) Note: Applicable to Frame C drives only. S (L2) Three-Phase AC Input R (L1) Power Off Power On Power Source DB Resistor Thermostat PowerFlex 4M Adjustable Frequency Drive FRN 1.xx — 2.xx User Manual Publication 22F-UM001D-EN-E…
  • Page 94
    4.9 (11) 1321-3R25-B 183 (7.20) 147 (5.80) 89 (3.50) 60 (2.35) 76 (3.00) 6.4 (14) 1321-3R35-A 193 (7.60) 146 (5.76) 91 (3.60) 66 (2.60) 76 (3.00) 6.3 (14) PowerFlex 4M Adjustable Frequency Drive FRN 1.xx — 2.xx User Manual Publication 22F-UM001D-EN-E…
  • Page 95
    Catalog Numbers: 22F-RF010-AL; 22F-RF9P5-AS, 22F-RF9P5-AL; 22F-RF6P0-AS, 22F-RF6P0-AL 72.0 (2.83) 50.0 (1.97) 31.0 (1.22) 54.0 (2.13) 229.0 (9.02) 218.5 (8.60) 218.5 (8.60) 19.0 5.5 (0.22) (0.75) 24.0 (0.94) PowerFlex 4M Adjustable Frequency Drive FRN 1.xx — 2.xx User Manual Publication 22F-UM001D-EN-E…
  • Page 96
    Catalog Numbers: 22F-RF025-BL; 22F-RF021-BS, 22F-RF021-BL; 22F-RF012-BS, 22F-RF012-BL 101.0 (3.98) 50.0 (1.97) 27.0 (1.06) 74.0 (2.91) 229.0 (9.02) 216.0 (8.50) 216.0 (8.50) 15.0 5.5 (0.22) (0.59) 24.0 (0.94) PowerFlex 4M Adjustable Frequency Drive FRN 1.xx — 2.xx User Manual Publication 22F-UM001D-EN-E…
  • Page 97
    Catalog Number: 22F-RF039-CS, 22F-RF039-CL; 22F-RF026-CS, 22F-RF026-CL 130.0 (5.12) 60.0 (2.36) 32.0 (1.26) 90.0 (3.54) 309.0 (12.17) 309.0 (12.17) 297.0 297.0 (11.69) (11.69) 5.5 (0.22) 17.0 (0.67) 30.0 (1.18) PowerFlex 4M Adjustable Frequency Drive FRN 1.xx — 2.xx User Manual Publication 22F-UM001D-EN-E…
  • Page 98
    Figure B.8 Remote (Panel Mount) HIM – Dimensions are in millimeters and (inches) Catalog Number: 22-HIM-C2 17.6 (0.69) (4.09) (8.66) 2.9m (3.07) (2.60) (7.64) (4.92) 60.5 (2.38) 19.1 (1.50) (0.75) (0.19) PowerFlex 4M Adjustable Frequency Drive FRN 1.xx — 2.xx User Manual Publication 22F-UM001D-EN-E…
  • Page 99
    (3.66) (7.09) (2.64) (2.36) (6.06) 19.1 (3.03) (0.75) (0.19) 23.5 (0.93) Important: The 22-HIM-C2S is smaller than the 22-HIM-C2 and cannot be used as a direct replacement. PowerFlex 4M Adjustable Frequency Drive FRN 1.xx — 2.xx User Manual Publication 22F-UM001D-EN-E…
  • Page 100
    Figure B.10 NEMA Type 1 Bezel – Dimensions are in millimeters and (inches) Catalog Number: 22-HIM-B1 11.1 (0.44) (3.66) 25.2 (0.99) (7.09) (2.64) (2.36) (6.06) 19.1 (3.03) (0.75) (0.19) 23.5 (0.93) PowerFlex 4M Adjustable Frequency Drive FRN 1.xx — 2.xx User Manual Publication 22F-UM001D-EN-E…
  • Page 101: Network Wiring

    PowerFlex 4M drives support the RS485 (DSI) protocol to allow efficient operation with Rockwell Automation peripherals. In addition, some Modbus functions are supported to allow simple networking. PowerFlex 4M drives can be multi-dropped on an RS485 network using Modbus protocol in RTU mode. Controller For information regarding DeviceNet or other communication protocols, refer to the appropriate user manual.

  • Page 102
    (1 foot). • Network wiring should only cross power wires at a right angle. Control Terminal 16 on the PowerFlex 4M must also be connected to PE ground (there are two PE terminals on the drive). See Figure 1.5 for more information.
  • Page 103: Parameter Configuration

    RS485 (DSI) Protocol Parameter Configuration The following PowerFlex 4M parameters are used to configure the drive to operate on a network. Parameter Details Reference P106 [Start Source] Set to 5 “RS485 (DSI) Port” if Start is controlled from Page 3-9 the network.

  • Page 104: Writing (06) Logic Command Data

    RS485 (DSI) Protocol Writing (06) Logic Command Data The PowerFlex 4M drive can be controlled via the network by sending Function Code 06 writes to register address 8192 (Logic Command). P106 [Start Source] must be set to 5 “RS485 (DSI) Port” in order to accept the commands.

  • Page 105: Writing (06) Reference

    RS485 (DSI) Protocol Writing (06) Reference The Speed Reference to a PowerFlex 4M drive can be controlled via the network by sending Function Code 06 writes to register address 8193 (Reference). P108 [Speed Reference] must be set to 5 “RS485 (DSI) Port”…

  • Page 106: Reading (03) Feedback

    Returns the same data as Reading (03) Parameter d001 [Output Freq]. Reading (03) Drive Error Codes The PowerFlex 4M Error Code data can be read via the network by sending Function Code 03 reads to register address 8449 (Drive Error Codes).

  • Page 107: Reading (03) And Writing (06) Drive Parameters

    For example, a decimal “1” is used to address Parameter d001 [Output Freq] and decimal “39” is used to address Parameter P109 [Accel Time 1]. Additional Information Refer to for additional information. http://www.ab.com/drives/ PowerFlex 4M Adjustable Frequency Drive FRN 1.xx — 2.xx User Manual Publication 22F-UM001D-EN-E…

  • Page 108
    RS485 (DSI) Protocol Notes: PowerFlex 4M Adjustable Frequency Drive FRN 1.xx — 2.xx User Manual Publication 22F-UM001D-EN-E…
  • Page 109: Rj45 Dsi Splitter Cable

    Appendix RJ45 DSI Splitter Cable The PowerFlex 4M drive provides a RJ45 port to allow the connection of a single peripheral device. The RJ45 DSI Splitter Cable can be used to connect a second DSI peripheral device to the drive.

  • Page 110: Dsi Cable Accessories

    RJ45 Two-Position Terminal Block Adapter – Catalog Number: AK-U0-RJ45-TB2P (PIN 5) PIN 8 (PIN 4) PIN 1 RJ45 Adapter with Integrated Termination Resistor – Catalog Number: AK-U0-RJ45-TR1 PIN 8 PIN 1 PowerFlex 4M Adjustable Frequency Drive FRN 1.xx — 2.xx User Manual Publication 22F-UM001D-EN-E…

  • Page 111: Connecting An Rs-485 Network

    4 and 5 only. Both the Master (M) and Slave (S) ports on the RJ45 Splitter Cable operate as standard RS-485 ports in this configuration. PowerFlex 4M Adjustable Frequency Drive FRN 1.xx — 2.xx User Manual Publication 22F-UM001D-EN-E…

  • Page 112
    RJ45 DSI Splitter Cable Notes: PowerFlex 4M Adjustable Frequency Drive FRN 1.xx — 2.xx User Manual Publication 22F-UM001D-EN-E…
  • Page 113
    Filter, RFI, 1-6 Dimensions Frame Designations, P-2, A-1, B-6 Drive, B-6 Fuses Minimum Clearances, 1-2 Input, 1-7 Display, 2-3 Ratings, A-1 Display Group Parameters, 3-3 Distribution Systems, Ungrounded, PowerFlex 4M Adjustable Frequency Drive FRN 1.xx — 2.xx User Manual Publication 22F-UM001D-EN-E…
  • Page 114
    RWR (Reflective Wave Reducer), 1-10 Opening the Cover, 1-1 Operating Temperatures, 1-2 Safety Ground, 1-5 Operator Interface, 2-3 Shielded Power Cables, 1-10 OverVoltage Fault, 4-3 Short Circuit Protection, 1-7 PowerFlex 4M Adjustable Frequency Drive FRN 1.xx — 2.xx User Manual Publication 22F-UM001D-EN-E…
  • Page 115
    Ungrounded Supply, 1-3 Unshielded Power Cables, 1-9 Watts Loss, A-5 Wiring, 1-1 Block Diagram, 1-14 I/O, 1-13 I/O Examples, 1-15, 1-18 Potentiometer, 1-15 Power, 1-9 PTC Example, 1-15 PowerFlex 4M Adjustable Frequency Drive FRN 1.xx — 2.xx User Manual Publication 22F-UM001D-EN-E…
  • Page 116
    Index-4 Notes: PowerFlex 4M Adjustable Frequency Drive FRN 1.xx — 2.xx User Manual Publication 22F-UM001D-EN-E…
  • Page 118
    www.rockwellautomation.com Power, Control and Information Solutions Headquarters Americas: Rockwell Automation, 1201 South Second Street, Milwaukee, WI 53204-2496 USA, Tel: (1) 414.382.2000, Fax: (1) 414.382.4444 Europe/Middle East/Africa: Rockwell Automation, Vorstlaan/Boulevard du Souverain 36, 1170 Brussels, Belgium, Tel: (32) 2 663 0600, Fax: (32) 2 663 0640 Asia Pacific: Rockwell Automation, Level 14, Core F, Cyberport 3, 100 Cyberport Road, Hong Kong, Tel: (852) 2887 4788, Fax: (852) 2508 1846 Publication 22F-UM001D-EN-E –…

Ремонт частотного преобразователя Rockwell Automation Allen Bradley Powerflex в

  • Особенности ремонта частотных преобразователей Allen Bradley
  • Программирование, настройка частотного преобразователя Allen Bradley
  • Ошибки частотного преобразователя Allen Bradley
  • Коды ошибок частотного преобразователя Allen Bradley
  • Частотный преобразователь Allen Bradley инструкция на русском, скачать
  • Схемы подключения частотных преобразователей Allen Bradley
  • Ремонт частотных преобразователей Allen Bradley в сервисном центре
  • Как заказать ремонт частотного преобразователя Allen Bradley

Ремонт частотного преобразователея Rockwell Automation Allen Bradley Powerflex

Ремонт частотного преобразователя Rockwell Automation Allen Bradley Powerflex известного американского производителя промышленной электроники, впрочем, как и ремонт частотников выпущенными под другими брендами имеет ряд особенностей в силу своего конструктива. Частотные преобразователи, точнее их начинка делятся на две части:

  1. Аппаратная часть,
  2. Программная часть.

Приводы данного производителя не являются исключением из правил, именно поэтому ремонт частотного преобразователя Allen Bradley имеет точно такой же ряд особенностей, как и у других преобразователей.

Диагностировать ту или иную неисправность помогают коды ошибок частотного преобразователя, которые отображаются на небольшом дисплее, расположенном на лицевой панели частотника.

Ремонт частотных преобразователей Rockwell Automation Allen Bradley Powerflex, впрочем, как и любых других частотников выпущенных под другими брендами всегда начинается с аппаратной части, после успешного ремонта аппаратной части наступает очередь программной.

Настройка частотного преобразователя Allen Bradley прописана в инструкции завода производителя, для каждой серии частотных преобразователей настройка будет индивидуальной, так как каждая линейка преобразователей решает свои собственные задачи, этим обусловливается широкая номенклатура данного промышленного оборудования. Но все же есть определенная последовательность настройки привода, которая относится ко всем частотным преобразователям, любого бренда.

Программирование, настройка частотного преобразователя Allen Bradley

Программирование частотных преобразователей Rockwell Automation Allen Bradley Powerflex (настройка) происходит в рамках установленных производителем правил, существует общий алгоритм по настройке (программированию частотных преобразователей), который относится ко всем производителям данного промышленного оборудования. Ниже представлена пошаговая инструкция по настройке частотных преобразователей Allen Bradley и подобного промышленного оборудования других брендов.

Ремонт частотного преобразователея Rockwell Automation Allen Bradley Powerflex

  1. Выбор режима управления приводом (управление по показанию датчиков, дистанционное управление, дистанционное управление).
  2. В случае использования отдельного (выносного) монитора, настраивается вывод на него технической информации.
  3. Далее определяем конфигурацию подключения серводвигателя. На данной стадии задаются такие параметры как- возможность применения обратной связи либо без ее применения, а в память блока заносятся данные по: величине крутящего момента, мощности потребителей, номинальное значения частоты, напряжение, ток и скорости вращения ротора.
  4. Программируется минимально допустимая величина напряжения и частоты, а также время ускорения ротора от ноля до номинального значения.
  5. И в завершении, в программу управления частотным преобразователем Allen Bradley вносятся функциональные данные со значениями отдельных клемм и особенностями сигналов. Отмечаются действия оборудования, выполняющиеся автоматически при отсутствии информации поступающей в оперативном режиме с датчика.

В некоторых преобразователях частоты существует пункт наличия/отсутствия фильтра в цепи питания двигателя. Этот пункт отвечает за подключение различных видов нагрузок, в том случае, когда возможно выбрать нормальное или инверсное изменение частоты при повышении уровня сигнала обратной связи.

Ошибки частотного преобразователя Allen Bradley

Ремонт частотных преобразователей Rockwell Automation Allen Bradley Powerflex

В процессе работы выходит из строя даже самое надежное промышленное оборудование. Частотники в наше время, нашли широкое применение абсолютно во всех сферах промышленности, управляя как мини моторами в оргтехнике, так и гигантскими двигателями в горнодобывающей промышленности.

Для простоты общения со столь сложной электроникой все частотные преобразователи оснащены небольшими дисплеями с помощью которых выводятся информационные сообщения с кодами ошибок, расшифровав которые можно сразу же узнать причину ее возникновения. Если учесть распространенность данной промышленной электроники, то появляется острая нужда в расшифровке кодов ошибок частотных преобразователей. В этой статье мы рассмотрим одного из самых известных производителей промышленной электроники имеющему уважение во всем мире, Rockwell Automation Allen Bradley и серию частотных преобразователей Powerflex 520.

Существует несколько видов ошибок, некоторые из них можно устранить автоматически, а некоторые возможно исправить только, обратившись в специализированный сервисный центр. В руководстве пользователя прописаны все коды ошибок частотного преобразователя Rockwell Automation Allen Bradley Powerflex 520 и их расшифровка.

Коды ошибок частотного преобразователя Allen Bradley Powerflex 520

Ошибка – это условие, останавливающее преобразователь. Существует два типа аварий.

Тип Ошибка Описание
1 С автоматическим сбросом/запуском Если произошла ошибка этого типа, а для параметра A541 [Auto Rstrt Tries] установлено значение больше «0», запускается настраиваемый пользователем таймер A542 [Auto Rstrt Delay]. Когда таймер достигает нуля, преобразователь предпринимает попытку автоматического сброса ошибки. И в том случае, если условия, вызвавшего ошибку, больше не существует, произойдёт сброс ошибки и преобразователь снова будет запущен.
2 Несбрасываемая Этот тип ошибки может потребовать ремонта преобразователя или двигателя, он может быть вызван неправильным подключением кабелей или допущенными в программе ошибками. Для сброса ошибки необходимо устранить её причину.
Поз. Ошибка Тип Описание
F000 Нет ошибки Ошибка отсутствует.
F002 Дополнительный вход 1 Вход внешнего отключения (вспом.).
F003 Потеря питания 2 В однофазном режиме обнаружена чрезмерная нагрузка.
F004 Пониженное напряжение 1 Напряжение шины постоянного тока упало ниже минимального значения.
F005 Перенапряжение 1 Напряжение на шине постоянного тока превышает максимальное значение.
F006 Двигатель заблокирован 1 Преобразователь не подходит для разгона или торможения двигателя.
F007 Перегрузка двигателя 1 Сработал встроенный электронный ограничитель нагрузки.
F008 Перегрев радиатора 1 Температура радиатора/модуля питания вышла за пределы допуска.
F009 Перегрев контр.узла 1 Температура модуля управления превышает заданное значение.
F012 Превышение аппаратного тока 2 Выходной ток преобразователя превысил допустимый предел.
F013 Ошибка заземления 2 Обнаружено замыкание на землю одной или нескольких выходных клемм преобразователя.
F015(1) Потеря нагрузки 2 Выходной ток крутящего момента ниже значения, установленного параметром A490 [Load Loss Level], в течение времени, превышающего установленное параметром A491 [Load Loss Time].
F021 Обрыв фазы вывода 1 Обрыв фазы вывода (если включена). Настраивается при помощи A557 [Out Phas Loss En].
F029 Обрыв аналог. ввода 1 Для аналогового входа задано сообщение об ошибке в случае пропадания сигнала. Пропал сигнал. Настраивается при помощи t094 [Anlg In V Loss] или t097 [Anlg In mA Loss].
F033 Попытки авт. перезапуска 2 Предпринятые преобразователем попытки сброса ошибки и продолжения работы оканчивались неудачей столько раз, сколько было задано в параметре A541 [Auto Rstrt Tries].
F038
F039
F040
Фаза U на землю
Фаза V на землю
Фаза W на землю
2 Ошибка замыкания фазы на землю была обнаружена между преобразователем и двигателем в этой фазе.
F041
F042
F043
Короткое замыкание фаз U и V
Короткое замыкание фаз U и W
Короткое замыкание фаз V и W
2 Между двумя данными клеммами обнаружено превышение по току.
F048 Запись в параметры значений по умолчанию 1 Преобразователь подал команду записи в ЭППЗУ значений по умолчанию.
F059(1) Откр.безопасн. 1 Отключены оба защитных входа (Safety 1, Safety 2). Настраивается при помощи t105 [Safety Open En].
F063 Превышение по току 1 Запрограммированное значение A486, A488 [Shear Pinx Level] превышено на период, превышающий время, заданное в A487, A489 [Shear Pin x Time].
F064 Перегрузка преобразователя 2 Превышена допустимая перегрузка преобразователя.
F070 Блок питания 2 Обнаружена ошибка питания преобразователя.
F071 Потеря сети DSI 2 Управление по Modbus или каналу связи DSI прервано.
F072 Потеря сети Opt 2 Управление по удалённой сети платы выбора подключений прервано.
F073(1) Потеря сети EN 2 Управление через встроенный адаптер EtherNet/IP прервано.
F080 Ошибка автоподстройки 2 Произошла ошибка функции автонастройки или работа функции отменена пользователем.
F081 Потеря DSI Comm 2 Связь между преобразователем и ведущим устройством Modbus или DSI прервана.
F082 Потеря Opt Comm 2 Связь между преобразователем и сетевой платой выбора подключений прервана.
F083(1) Потеря EN Comm 2 Внутренняя связь между преобразователем и встроенным адаптером EtherNet/IP прервана.
F091(1) Потеря энкодера 2 Необходим дифференциальный энкодер. Отсутствует сигнал в одном из двух каналов энкодера.
F094 Потеря функции 2 Вход «Замораживание-запуск» (потеря функции) не активен, вход к программируемой клемме открыт.
F100 Ошибка контрольной суммы параметра 2 Энергонезависимая память параметров преобразователя повреждена.
F101 Внешняя память 2 Внешняя энергонезависимая память повреждена.
F105 Ошибка соед. контр. узла 2 Модуль управления отсоединён во время включения преобразователя.
F106 Несовместим. контр. уз. – блок пит. 2 Модуль управления не может распознать модуль питания.
F107 Замен. контр. уз. – блок пит. 2 Модуль управления установлен на модуль питания с отличающейся номинальной мощностью.
F109 Несоотв. контр. уз. – блок пит. 2 Модуль управления установлен на модуль питания с отличающейся номинальной мощностью.
F110 Мембранная клавиатура 2 Ошибка/отсоединение мембранной клавиатуры.
F111(1) Защитное оборудование 2 Аппаратная ошибка включения защитного оборудования. Один из защитных входов не включён.
F114 Сбой микропроц. 2 Сбой микропроцессора
F122 Ошибка платы ввода-вывода 2 Обнаружен сбой в секции ввода- вывода и управления преобразователя.
F125 Требуется обновление флеш-памяти 2 Встроенное ПО в преобразователе повреждено, не согласовано или несовместимо с аппаратурой.
F126 NonRecoverablErr 2 Была обнаружена неустранимая ошибка встроенного ПО или аппаратуры. Преобразователь был автоматически остановлен и выполнен сброс.
F127 DSIFlashUpdatReq 2 Была обнаружена существенная проблема со встроенным ПО, и преобразователь работает с использованием резервного встроенного ПО, которое поддерживает только связь DSI.

(1) Эта ошибка неприменима к преобразователям PowerFlex 523.

Частотный преобразователь Allen Bradley инструкция на русском, скачать

Все настройки частотных преобразователей Rockwell Automation Allen Bradley Powerflex приведены в технической документации ниже в удобном формате (PDF) который можно скачать на свой компьютер, распечатать или просто открыть на нашем сайте.

Промышленный частотный преобразователь Allen Bradley инструкции, скачать русскоязычные и англоязычные версии в формате PDF.

Частотный преобразователь Allen Bradley PowerFlex 4 инструкция

podkategorij Скачать PDF

Частотный преобразователь Allen Bradley PowerFlex 4M инструкция

podkategorij Скачать PDF

Частотный преобразователь Allen Bradley PowerFlex 40 инструкция

podkategorij Скачать PDF

Частотный преобразователь Allen Bradley PowerFlex 40P инструкция

podkategorij Скачать PDF

Частотный преобразователь Allen Bradley PowerFlex 70 инструкция

podkategorij Скачать PDF

Частотный преобразователь Allen Bradley PowerFlex 400 инструкция

podkategorij Скачать PDF

Частотный преобразователь Allen Bradley PowerFlex 520 инструкция на руссокм

podkategorij Скачать PDF

Частотный преобразователь Allen Bradley PowerFlex 520 технические характеристики на русском

podkategorij Скачать PDF

Частотный преобразователь Allen Bradley PowerFlex 700AFE инструкция на русском

podkategorij Скачать PDF

Частотный преобразователь Allen Bradley PowerFlex 700L инструкция

podkategorij Скачать PDF

Частотный преобразователь Allen Bradley PowerFlex 700 инструкция на русском

podkategorij Скачать PDF

Частотный преобразователь Allen Bradley PowerFlex 750 инструкция на русском

podkategorij Скачать PDF

Частотный преобразователь Allen Bradley PowerFlex 750 инструкция по монтажу на русском

podkategorij Скачать PDF

Частотный преобразователь Allen Bradley PowerFlex-750 инструкция по программированию на русском

podkategorij Скачать PDF

Схемы подключения частотных преобразователей Allen Bradley

Схемы подключений частотных преобразователей Allen Bradley могут отличатся друг от друга даже если эти преобразователи относятся ко одной линейке. Схема подключения преобразователя зависит от потребляемой частотным преобразователем нагрузки или питающей сети к которой подключается частотник 200V – 380V, а также от оборудования с которым предполагается работа данного частотника.

Ниже приведены схемы подключения частотного преобразователя Allen Bradley.

Схема подключения частотного преобразователя Allen Bradley PowerFlex-4

Схема подключения частотного преобразователя Allen Bradley PowerFlex-4M

Схема подключения частотного преобразователя Allen Bradley PowerFlex 4

Схема подключения частотного преобразователя Allen Bradley PowerFlex 4M

Схема подключения частотного преобразователя Allen Bradley PowerFlex-40

Схема подключения частотного преобразователя Allen Bradley PowerFlex 40

Ремонт частотных преобразователей Allen Bradley в сервисном центре

Ремонт частотного преобразователея Rockwell Automation Allen Bradley Powerflex

Сервисный центр «Кернел» производит ремонт частотных преобразователей Rockwell Automation Allen Bradley Powerflex в с 2002 года. За время существования компании наши сотрудники накопили колоссальный опыт в ремонте преобразователей частоты такого известного производителя как Ален Бредли. Ремонт подобного промышленного оборудования ответственное и сложное занятие, требующие максимальной отдачи, профессионализма и максимально полной материальной базе.

Специалисты нашего сервисного центра максимальное внимание уделяют качеству исполнения ремонта, программирования и настройке промышленных преобразователей частоты, не зависимо от производителя данного промышленного оборудования. Именно поэтому мы смело даем гарантию на ремонт частотных преобразователей Rockwell Automation Allen Bradley Powerflex и запасные части замененные в процессе ремонта шесть месяцев.

Ремонт частотных преобразователей Allen Bradley в производится исключительно с использованием оригинальных запасных частей, на компонентном уровне с применением высокотехнологичного оборудования, квалифицированным персоналом с инженерным образованием.

Мы ремонтируем все линейки частотных преобразователей Allen Bradley в том числе:

Серия ПЧ Типы частотных преобразователей Rockwell Automation Allen Bradley Powerflex
PowerFlex 755 20G11GD2P1JA0NNNNN; 20G11GD3P4JA0NNNNN; 20G11GD5P0JA0NNNNN; 20G11GD8P0JA0NNNNN; 20G11GD011JA0NNNNN; 20G11GD014JA0NNNNN; 20G11GD022JA0NNNNN; 20G11GD027JA0NNNNN; 20G11GD034JA0NNNNN; 20G11GD040JA0NNNNN; 20G11GD052JA0NNNNN; 20G11GD065JA0NNNNN; 20G11GD077JA0NNNNN; 20G1AJD430JN0NNNNN; 20G1AJD485JN0NNNNN; 20G1AJD545JN0NNNNN; 20G1AJD617JN0NNNNN; 20G1AJD710JN0NNNNN; 20G1AJD740JN0NNNNN; 20G11JD800JN0NNNNN; 20G11JD960JN0NNNNN; 20G11JD1K0JN0NNNNN; 20G11JD1K2JN0NNNNN; 20G11JD1K3JN0NNNNN; 20G11JD1K4JN0NNNNN; 20G11JD1K5JN0NNNNN; 20G11JD2K0JN0NNNNN; 20G11RB2P2JA0NNNNN; 20G11RB4P2JA0NNNNN; 20G11RB6P8JA0NNNNN; 20G11RB9P6JA0NNNNN; 20G11RB015JA0NNNNN; 20G11NB2P2JA0NNNNN; 20G11NB4P2JA0NNNNN; 20G11NB6P8JA0NNNNN; 20G11NB9P6JA0NNNNN; 20G11NB015JA0NNNNN; 20G11NB022JA0NNNNN; 20G11NB028JA0NNNNN; 20G11NB042JA0NNNNN; 20G11NB054JA0NNNNN; 20G11NB070JA0NNNNN; 20G11NB080JA0NNNNN
PowerFlex 753 20F11RB2P2JA0NNNNN; 20F11RB4P2JA0NNNNN; 20F11RB6P8JA0NNNNN; 20F11RB9P6JA0NNNNN; 20F11RB015JA0NNNNN; 20F11NB2P2JA0NNNNN; 20F11NB4P2JA0NNNNN; 20F11NB6P8JA0NNNNN; 20F11NB9P6JA0NNNNN; 20F11NB015JA0NNNNN; 20F11NB022JA0NNNNN; 20F11NB028JA0NNNNN; 20F11NB042JA0NNNNN; 20F11NB054JA0NNNNN; 20F11NB070JA0NNNNN; 20F11NB080JA0NNNNN; 20F11GB2P2JA0NNNNN; 20F11GB4P2JA0NNNNN; 20F11GB6P8JA0NNNNN; 20F11GB9P6JA0NNNNN; 20F11GB015JA0NNNNN; 20F11GB022JA0NNNNN; 20F11GB028JA0NNNNN; 20F11GB042JA0NNNNN; 20F11GB054JA0NNNNN; 20F11GB070JA0NNNNN; 20F11FB2P2JA0NNNNN; 20F11FB4P2JA0NNNNN; 20F11FB6P8JA0NNNNN; 20F11FB9P6JA0NNNNN; 20F11FB015JA0NNNNN; 20F11FB022JA0NNNNN; 20F11FB028JA0NNNNN; 20F11FB042JA0NNNNN; 20F11FB054JA0NNNNN; 20F11FB070JA0NNNNN; 20F11FB080JA0NNNNN
PowerFlex 755TL
PowerFlex 755TR
PowerFlex 755TM
20G1xxC302xNxNNNNN-Cx-Px; 20G1xxC367xNxNNNNN-Cx-Px; 20G1xxC460xNxNNNNN-Cx-Px; 20G1xxC540xNxNNNNN-Cx-Px; 20G1xxC585xNxNNNNN-Cx-Px; 20G1xxC650xNxNNNNN-Cx-Px; 20G1xxC750xNxNNNNN-Cx-Px; 20G1xxC770xNxNNNNN-Cx-Px; 20G1xxC920xNxNNNNN-Cx-Px; 20G1xxC1K0xNxNNNNN-Cx-Px; 20G1xxC1K1xNxNNNNN-Cx-Px; 20G1xxD302xNxNNNNN-Cx-Px; 20G1xxD505xNxNNNNN-Cx-Px; 20G1xxD710xNxNNNNN-Cx-Px; 20G1xxD960xNxNNNNN-Cx-Px; 20G1xxD1K3xNxNNNNN-Cx-Px; 20G1xxD1K6xNxNNNNN-Cx-Px; 20G1xxD2K6xNxNNNNN-Cx-Px; 20G1xxD3K4xNxNNNNN-Cx-Px; 20G1xxE242xNxNNNNN-Cx-Px; 20G1xxE295xNxNNNNN-Cx-Px; 20G1xxE435xNxNNNNN-Cx-Px; 20G1xxE690xNxNNNNN-Cx-Px; 20G1xxE980xNxNNNNN-Cx-Px; 20G1xxE1K2xNxNNNNN-Cx-Px; 20G1xxE2K4xNxNNNNN-Cx-Px; 20G1xxF215xNxNNNNN-Cx-Px; 20G1xxF330xNxNNNNN-Cx-Px; 20G1xxF415xNxNNNNN-Cx-Px; 20G1xxF650xNxNNNNN-Cx-Px; 20G1xxF920xNxNNNNN-Cx-Px; 20G1xxF1K4xNxNNNNN-Cx-Px; 20G1xxF1K8xNxNNNNN-Cx-Px; 20G1xxF2K3xNxNNNNN-Cx-Px;
PowerFlex 70 20AB2P2A0AYNNNC0; 20AB2P2A0AYNANC0; 20AB4P2A0AYNNNC0; 20AB4P2A0AYNANC0; 20AB6P8A0AYNNNC0; 20AB6P8A0AYNANC0; 20AB9P6A0AYNNNC0; 20AB9P6A0AYNANC0; 20AB015A0AYNANC0; 20AB022A0AYNANC0; 20AB028A0AYNANC0; 20AB042A0AYNANC0; 20AB054A0AYNANC0; 20AB070A0AYNANC0; 20AC1P3A0AYNNNC0; 20AC1P3A0AYNANC0; 20AC2P1A0AYNNNC0; 20AC2P1A0AYNANC0; 20AC3P5A0AYNNNC0; 20AC3P5A0AYNANC0; 20AC5P0A0AYNNNC0; 20AC5P0A0AYNANC0; 20AC8P7A0AYNNNC0; 20AC8P7A0AYNANC0; 20AC011A0AYNANC0; 20AC015A0AYNANC0; 20AC043A0AYNANC0; 20AE0P9A0AYNNNC0; 20AE3P9A0AYNNNC0; 20AE011A0AYNNNC0; 20AE022A0AYNNNC0; 20AE041A0AYNANC0; 20AB2P2C3AYNNNC0; 20AB022C3AYNANC0; 20AB070C3AYNANC0; 20AC2P1C3AYNNNC0; 20AD2P1C3AYNANC0; 20AD011C3AYNANC0; 20AC037C3AYNANC0; 20AD052C3AYNANC0; 20AC072C3AYNANC0
PowerFlex 523 25A-V1P6N104; 25A-V2P5N104; 25A-V4P8N104; 25A-V6P0N104; 25A-A1P6N104; 25A-A1P6N114; 25A-A2P5N104; 25A-A2P5N114; 25A-A4P8N104; 25A-A4P8N114; 25A-A8P0N104; 25A-A8P0N114; 25A-A011N104; 25A-A011N114; 25A-B1P6N104; 25A-B2P5N104; 25A-B5P0N104; 25A-B8P0N104; 25A-B011N104; 25A-B017N104; 25A-B024N104; 25A-B032N104; 25A-B048N104; 25A-B062N104; 25A-D1P4N104; 25A-D2P3N114; 25A-D4P0N104; 25A-D6P0N114; 25A-D010N104; 25A-D013N114; 25A-D017N104; 25A-D024N114; 25A-D030N104; 25A-D037N114; 25A-E0P9N104; 25A-E1P7N104; 25A-E3P0N104; 25A-E4P2N104; 25A-E6P6N104; 25A-E9P9N104; 25A-E012N104; 25A-E019N104; 25A-E022N104; 25A-E027N104; 25A-E032N104
PowerFlex 525 25B-V2P5N104; 25B-V4P8N104; 25B-V6P0N104; 25B-A2P5N104; 25B-A2P5N114; 25B-A4P8N104; 25B-A4P8N114; 25B-A8P0N104; 25B-A8P0N114; 25B-A011N104; 25B-A011N114; 25B-B2P5N104; 25B-B5P0N104; 25B-B8P0N104; 25B-B011N104; 25B-B017N104; 25B-B024N104; 25B-B032N104; 25B-B048N104; 25B-B062N104; 25B-D1P4N104; 25B-D2P3N114; 25B-D4P0N104; 25B-D6P0N114; 25B-D010N104; 25B-D013N114; 25B-D017N104; 25B-D024N114; 25B-D030N104; 25B-D037N114; 25B-E0P9N104; 25B-E1P7N104; 25B-E3P0N104; 25B-E4P2N104; 25B-E6P6N104; 25B-E9P9N104; 25B-E012N104; 25B-E022N104; 25B-E032N104
PowerFlex 527 25C-V2P5N104; 25C-V4P8N104; 25C-V6P0N104; 25C-A2P5N104; 25C-A4P8N104; 25C-A8P0N104; 25C-A011N104; 25C-A2P5N114; 25C-A4P8N114; 25C-A8P0N114; 25C-A011N114; 25C-B2P5N104; 25C-B5P0N104; 25C-B8P0N104; 25C-B011N104; 25C-B017N104; 25C-B024N104; 25C-B032N104; 25C-B048N104; 25C-B062N104; 25C-D1P4N104; 25C-D2P3N104; 25C-D4P0N104; 25C-D6P0N104; 25C-D010N104; 25C-D013N104; 25C-D017N104; 25C-D024N104; 25C-D030N104; 25C-D1P4N114; 25C-D2P3N114; 25C-D4P0N114; 25C-D6P0N114; 25C-D010N114; 25C-D013N114; 25C-D017N114; 25C-D024N114; 25C-D030N114; 25C-D037N114; 25C-D043N114; 25C-E0P9N104; 25C-E1P7N104; 25C-E3P0N104; 25C-E4P2N104; 25C-E6P6N104; 25C-E9P9N104; 25C-E012N104; 25C-E019N104; 25C-E022N104; 25C-E027N104; 25C-E032N104
PowerFlex 4M 22F-V1P6N103; 22F-V2P5N103; 22F-V4P5N103; 22F-V6P0N103; 22F-A1P6N103; 22F-A1P6N113; 22F-A2P5N103; 22F-A2P5N113; 22F-A4P2N103; 22F-A4P2N113; 22F-A8P0N103; 22F-A8P0N113; 22F-A011N103; 22F-A011N113; 22F-B1P6N103; 22F-B2P5N103; 22F-B4P2N103; 22F-B8P0N103; 22F-B012N103; 22F-B017N103; 22F-B025N104; 22F-B033N104; 22F-D1P5N103; 22F-D1P5N113; 22F-D2P5N103; 22F-D2P5N113; 22F-D4P2N103; 22F-D4P2N113; 22F-D6P0N103; 22F-D6P0N113; 22F-D8P7N103; 22F-D8P7N113; 22F-D013N104; 22F-D013N114; 22F-D018N104; 22F-D018N114; 22F-D024N104; 22F-D024N114
PowerFlex 400 22C-B012N103; 22C-B012F103; 22C-B017N103; 22C-B017F103; 22C-B024N103; 22C-B024F103; 22C-B033N103; 22C-B033F103; 22C-B049A103; 22C-B065A103; 22C-B075A103; 22C-B090A103; 22C-B120A103; 22C-B145A103; 22C-D6P0N103; 22C-D6P0F103; 22C-D010N103; 22C-D010F103; 22C-D012N103; 22C-D012F103; 22C-D017N103; 22C-D017F103; 22C-D022N103; 22C-D022F103; 22C-D030N103; 22C-D030F103; 22C-D038A103; 22C-D045A103; 22C-D060A103; 22C-D072A103; 22C-D088A103; 22C-D105A103; 22C-D142A103; 22C-D170A103; 22C-D208A103; 22C-D260A103; 22C-D310A103; 22C-D370A103; 22C-D460A103
PowerFlex 4 22A-V1P5N104; 22A-V2P3N104; 22A-V4P5N104; 22A-V6P0N104; 22A-A1P4N103; 22A-A2P1N103; 22A-A3P6N103; 22A-A6P8N103; 22A-A9P6N103; 22A-A1P4N113; 22A-A2P1N113; 22A-A3P6N113; 22A-A6P8N113; 22A-A9P6N113; 22A-A1P5N114; 22A-A2P3N114; 22A-A4P5N114; 22A-A8P0N114; 22A-A1P5N104; 22A-A2P3N104; 22A-A4P5N104; 22A-A8P0N104; 22A-B1P5N104; 22A-B2P3N104; 22A-B4P5N104; 22A-B8P0N104; 22A-B012N104; 22A-B017N104; 22A-D1P4N104; 22A-D2P3N104; 22A-D4P0N104; 22A-D6P0N104; 22A-D8P7N104; 22B-A2P3N114
PowerFlex 40 22B-V2P3N104; 22B-V5P0N104; 22B-V6P0N104; 22B-A5P0N114; 22B-A8P0N114; 22B-A012N114; 22B-A2P3N104; 22B-A5P0N104; 22B-A8P0N104; 22B-A012N104; 22B-B2P3N104; 22B-B5P0N104; 22B-B8P0N104; 22B-B012N104; 22B-B017N104; 22B-B024N104; 22B-B033N104; 22B-D1P4N104; 22B-D2P3N104; 22B-D4P0N104; 22B-D6P0N104; 22B-D010N104; 22B-D012N104; 22B-D017N104; 22B-D024N104; 22B-E1P7N104; 22B-E3P0N104; 22B-E4P2N104; 22B-E6P6N104; 22B-E9P9N104; 22B-E012N104; 22B-E019N104
PowerFlex 40P 22D-B2P3N104; 22D-B5P0N104; 22D-B8P0N104; 22D-B012N104; 22D-B017N104; 22D-B024N104; 22D-B033N104; 22D-B2P3H204; 22D-B5P0H204; 22D-B8P0H204; 22D-B012H204; 22D-B017H204; 22D-B024H204; 22D-B033H204; 22D-B2P3F104; 22D-B5P0F104; 22D-B8P0F104; 22D-B012F104; 22D-B017F104; 22D-B024F104; 22D-B033F104; 22D-D1P4N104; 22D-D2P3N104; 22D-D4P0N104; 22D-D6P0N104; 22D-D010N104; 22D-D012N104; 22D-D017N104; 22D-D024N104; 22D-D1P4F104; 22D-D2P3F104; 22D-D4P0F104; 22D-D6P0F104; 22D-D010F104; 22D-D012F104; 22D-D017F104; 22D-D024F104; 22D-E1P7H204; 22D-E3P0H204; 22D-E4P2H204; 22D-E6P6H204; 22D-E9P9H204; 22D-E012H204; 22D-E019H204
PowerFlex 700 20BD011A3AYYADB0; 20BD8P0A3AYYAEB0; 20BD011A3NYNAED0; 20BD156A3ANNAED0; 20BC011A3AYYANC1; 20BD248A3AYNANC0; 20BH105A3AYNANA0; 20BD180A3ANNACB0; 20BC037A3AYNACA0; 20BE144A3AYNACD0; 20BC205A3ANNAEC0; 20BR156F0ANNAND0; 20BB015A3AYNBNB0; 20BD8P0A3NYNACD1; 20BB154A3ANNANB0; 20BB015A3AYNBEC0NNAD; 20BD077A3NYNANC0; 20BD180A3AYNACD0; 20BD8P0A3AYYACB0; 20BD8P0A3NYYAND0; 20BD180A3ANNADD1; 20BC022A3AYNANC1; 20BR180A3ANNANA0; 20BD125A3AYNAEB0; 20BE125A3ANNADD0; 20BR248A3AYNACC1; 20BE125A3ANNAND0; 20BC125A3ANNACA0; 20BC170A3NYNAEA0; 20BP105A3ANNAEC1; 20BP140F3ANNANC0; 20BD180A3ANNANC0NNAD; 20BP205A3ANNADC1; 20BD248A3ANNAEA0; 20BB154A3ANNACB0; 20BD8P0A3NYNADB0; 20BD125A3AYNAND0; 20BD248A3ANNAEB0; 20BD180A3ANNADD0; 20BD156A0NYNACC0
PowerFlex 700S 20DB015A3EYNACGNE; 20DD5P0A3NYYACGNE; 20DB022A3EYNACGNE; 20DB042A3EYNACGNE; 20DD077A3EYNANASE; 20DD3P4A3EYNACASE; 20DD180A3EYNAEASE; 20DC3P5A3EYNAEBSE; 20DR180A3NNNACHNE; 20DD027A3NYNANANE; 20DD052A3NYNANANE; 20DB4P2A0EYNANANE; 20DD5P0A3EYNAEBNE; 20DC037A0NYNANANE; 20DR156A0NNNACGNE; 20DD077A3EYNANDNK; 20DD052A0NYNANANE; 20DD027A0EYNANGNE; 20DD014A3NYYACBSE; 20DD034A0EYYANANE; 20DC8P7A0NYNANCNK; 20DR125A3ENNACASE; 20DD248A3ENNANGNE; 20DD027A3EYNACGNE; 20DD065A0NYNANANK; 20DH300N0ENNBNANK; 20LF705N0QNNJNB0KA; 20DD261A3EYNBEASE; 20DD156A0EYNACASE; 20DR125A0ENNACANE
PowerFlex 700L 21LC1K2N0NNNTEZ0WA; 20LD650N3ENNEEASEA; 20LD650ACENNACA0EA; 20LC1K2ACENNAN10WA; 20LD1K2ACENNAEA0EA; 20LD650A0NNNANBSEA; 20LD1K2ACENNANDSLA; 20LC1K2N0QNNJNC0LA; 20LF380N0QNNEND0LA; 20LD650ACENNAND0LA; 20LD650N0QNNENA0LA; 20LD360N3ENNADDCLA; 20LD650N0QNNEND0LA; 20LD650ACENNA2CSLA; 20LF380N3ENNLNCBLA; 20LD650A0ENNANA0EA; 20LD650N0NNNLEBSEA; 20LC180N3ENNACBAEABB; 20LE425N0QNNENA0LA; 20LF705N0QNNJNA0LA; 20LD650ACENNACABEA; 20LF380N0QNNENB0LA; 20LD1K2N0QNNJND0LA; 20LD650A0ENNAND0LA; 20LE425N0ENNLNASEA; 20LD1K2N0ENNJNASEA; 20LC1K2N0QNNJND0LA; 20LF380N0QNNENA0LA; 20LD360N0ENNANC0LA; 20LD650ACENNA6CSLA

В таблице указаны далеко не все типы частотных преобразователей Rockwell Automation Allen Bradley Powerflex ремонт которых выполняет сервисный центр «Кернел».

В случае выхода из строя преобразователя частоты на вашем производстве либо появились проблемы с приводом, которые вы не можете решить самостоятельно, мы всегда рады вам помочь. Специалисты нашего сервисного центра в минимальные сроки проведут глубокую диагностику с последующим ремонтом частотного преобразователя PowerFlex. Оставьте заказ на ремонт промышленного оборудования используя форму на сайте, либо свяжетесь с нашими менеджерами, сделать это очень просто.

Как заказать ремонт частотного преобразователя Allen Bradley

У вас остались вопросы, связанные с ремонтом частотных преобразователей Allen Bradley? Оставьте заявку на ремонт частотного преобразователя Rockwell Automation Allen Bradley Powerflex в нашим менеджерам. Связаться с ними можно несколькими способами:

  • Заказав обратный звонок (кнопка в правом нижнем углу сайта)
  • Посредством чата (кнопка расположена с левой стороны сайта)
  • Позвонив по номеру телефона:
    • +7(8482) 79-78-54;
    • +7(8482) 55-96-39;
    • +7(917) 121-53-01
  • Написав на электронную почту: 89171215301@mail.ru

Далеко не полный список производителей промышленной электроники и оборудования, ремонтируемой в нашей компании.

  • В начало статьи

Предложите, как улучшить StudyLib

(Для жалоб на нарушения авторских прав, используйте

другую форму
)

Ваш е-мэйл

Заполните, если хотите получить ответ

Оцените наш проект

1

2

3

4

5

Заказать оборудование Allen Bradley

Купить Allen Bradley powerflex ошибки в компании Олниса можно оптом или в розницу. Доставим Allen Bradley powerflex ошибки в любой регион России. Можем предложить точный аналог. Работаем напрямую с производителем, не используя посредников.

При работе промышленной электроники производителя Аллен-Брэдли могут возникать определённые ошибки. Чтобы быстро их устранить, необходима помощь наладчика оборудования или можно самостоятельно ознакомиться с инструкцией. Приборы максимально адаптированы для работы новичков и настроить их не составит большого труда.

Серия Allen Bradley PowerFlex представлена частотными преобразователями. Зная специфику их работы и наименование модельного ряда, можно быстро сориентироваться для устранения ошибок в промышленном секторе:

  • серия PowerFlex 1305;
  • серия PowerFlex 1332;
  • серия PowerFlex 70;
  • серия PowerFlex 700S;
  • серия PowerFlex 1333;
  • серия PowerFlex 1334;
  • серия PowerFlex 1336;
  • серия PowerFlex 1341;
  • серия PowerFlex 1351;
  • серия PowerFlex 527;
  • серия PowerFlex 4M;
  • серия PowerFlex 4;
  • серия PowerFlex 40;
  • серия PowerFlex 40P;
  • серия PowerFlex 1352;
  • серия PowerFlex 1361;
  • серия PowerFlex 160;
  • серия PowerFlex 755T;
  • серия PowerFlex 755 TL;
  • серия PowerFlex 755TR;
  • серия PowerFlex 755TM;
  • серия PowerFlex 753;
  • серия PowerFlex 755;
  • серия PowerFlex 700;
  • серия PowerFlex 700L;
  • серия PowerFlex 523;
  • серия PowerFlex 525;
  • серия PowerFlex 400.

Allen Bradley powerflex ошибки

Кодировка ошибки и ее значение

Для всех вышеперечисленных частотников наиболее характерны следующие шифры ошибок:

  • сбой F2 – ошибка входа в Auxiliary;
  • сбой F3 – нарушение или обрыв фазы сети при подключении;
  • сбой F4 – слишком низкий показатель электронапряжения в сети;
  • сбой F5 – слишком высокий показатель электронапряжения в сети;
  • сбой F6 – поломка двигателя, есть механические повреждения, мешающие нормальной работе устройства;
  • сбой F7 – перегрузка электромотора напряжением, опасность;
  • сбой F8 – начинает перегреваться радиатор;
  • сбой F12 – пиковый скачок напряжения с прицельным электроударом на аппарат;
  • сбой F13 – произошло короткое замыкание контакта заземления;
  • сбой F29 – аналоговый вход неисправен;
  • сбой F33 – невозможно переподключиться автоматически, превышен лимит авто запроса;
  • сбои в диапазоне F38-43 – сигнализируют о нарушениях работы фаз U, V, W и их коннекта между собой;
  • сбой F48 – аварийный сброс всех предустановленных автонастроек;
  • сбой F63 – сбой установки ПО;
  • сбой F64 – внезапная перезагрузка в процессе работы –неисправность системы;
  • сбой F70 – силовая часть аппарата вышла из строя;
  • сбой F71 – нарушена обратная связь с контролирующим устройством;
  • сбой F80 – автоматические корректировки более работают, требуется перезагрузка системы;
  • error F81 – неисправен порт RS-485;
  • сбой F100 – отказ подсчета суммы записанных параметров;
  • сбой F122 – плата ввода/вывода вышла из строя.

Это основной перечень, который легко устранить, следуя руководству по эксплуатации преобразователей частоты Аллен-Брэдли.

Allen Bradley powerflex ошибки

Покупка в «Олниса»

Выбор конкретного устройства и его настройка – задача специалиста или работника, ответственного за контроль прибора. Оригинальные устройства с длительной гарантией работы и полным сервисным обслуживанием на протяжении 12 месяцев от момента покупки вы найдете в нашем онлайн-каталоге.

Все приборы Allen Bradley можно приобрести с доставкой по России или любому другому городу на территории СНГ.

Reading (03) Drive Error

Codes

The PowerFlex 525 Error Code data can be read through the network by sending

Function Code 03 reads to register address 2101H (Drive Error Codes).

Drive Error Codes

Logic Status

Address (Decimal) Value (Decimal) Description

2101H (8449)

0

2

3

4

5

6

7

8

9

12

13

15

21

29

33

38

39

40

41

42

43

48

59

63

64

70

71

72

73

80

81

82

83

91

94

100

101

105

106

107

109

110

111

114

122

Rockwell Automation Publication 520-UM001A-EN-E — February 2013

RS485 (DSI) Protocol

No Fault

Auxiliary Input

Power Loss

Undervoltage

Overvoltage

Motor Stalled

Motor Overload

Heatsink Overtemperature

Control Module Overtemperature

HW Overcurrent (300%)

Ground Fault

Load Loss

Output Phase Loss

Analog Input Loss

Auto Restart Tries

Phase U to Ground Short

Phase V to Ground Short

Phase W to Ground Short

Phase UV Short

Phase UW Short

Phase VW Short

Parameters Defaulted

Safety Open

Software Overcurrent

Drive Overload

Power Unit Fail

DSI Network Loss

Option Card Network Loss

Embedded EtherNet/IP Adapter Network Loss

AutoTune Fail

DSI Communication Loss

Option Card Communication Loss

Embedded EtherNet/IP Adapter Communication Loss

Encoder Loss

Function Loss

Parameter Checksum Error

External Storage

Control Module Connect Error

Incompatible Control-Power Module

Unrecognized Control-Power Module

Mismatched Control-Power Module

Keypad Membrane

Safety Hardware

Microprocessor Failure

I/O Board Fail

Appendix C

179

31 января 2023 г. 15:55

Фото ПЧ Allen Bradley PowerFlex40

При работе промышленной электроники Allen Bradley в системах вентиляции, теплоснабжения или автоматизированном производственном оборудовании часто возникают неисправности, распознать которые можно считав коды ошибок и произведя расшифровку этих кодов по инструкции на конкретную модель электронного оборудования. Наиболее частое использование в промышленном оборудовании получили следующие частотные преобразователи фирмы Allen Bradley: PowerFlex, 1305 Series, 1332 Series, 1333 Series, 1334 Series, 1336 Series, 1341 Series, 1351 Series, 1352 Series, 1361 Series, 160 Series,. В свою очередь серия Allen Bradley PowerFlex включает в себя следующие модели: PowerFlex 755T, PowerFlex 755TL, PowerFlex 755TR, PowerFlex 755TM, PowerFlex 753, PowerFlex 755, PowerFlex 755T, PowerFlex 70, PowerFlex 700S, PowerFlex 700, PowerFlex 700L, PowerFlex 523, PowerFlex 525, PowerFlex 527, PowerFlex 4M, PowerFlex 4, PowerFlex 40, PowerFlex 40P, PowerFlex 400. Своевременная расшифровка ошибок может значительно ускорить диагностику и ремонт преобразователей частоты, подробнее об этом написано здесь.

Частотные преобразователи Allen Bradley имеют следующие распространенные ошибки:

Наиболее частые ошибки преобразователей Allen Bradley PowerFlex 40:

Ошибка F2 (error F2) — ошибка входа Auxiliary;
Ошибка F3 (error F3) — обрыв фазы на входе;
Ошибка F4 (error F4) — пониженное напряжение;
Ошибка F5 (error F5) — перенапряжение;
Ошибка F6 (error F6) — механическая неисправность двигателя;
Ошибка F7 (error F7) — перегрузка двигателя;
Ошибка F8 (error F8) — перегрев радиатора;
Ошибка F12 (error F12) — аппаратная перегрузка по току;
Ошибка F13 (error F13) — короткое замыкание на землю;
Ошибка F29 (error F29) — ошибка аналогового входа;
Ошибка F33 (error F33) — превышено количество попыток автоматического повторного включения — АПВ;
Ошибка F38 (error F38) — замыкание фазы U на землю на выходе ПЧ;
Ошибка F39 (error F39) — замыкание фазы V на землю на выходе ПЧ;
Ошибка F40 (error F40) — замыкание фазы W на землю на выходе ПЧ;
Ошибка F41 (error F41) — короткое замыкание между фазами UV;
Ошибка F42 (error F42) — короткое замыкание между фазами UW;
Ошибка F43 (error F43) — короткое замыкание между фазами VW;
Ошибка F48 (error F48) — параметры EEPROM были сброшены;
Ошибка F63 (error F63) — перегрузка по току по программной уставке;
Ошибка F64 (error F64) — перегрузка во время работы;
Ошибка F70 (error F70) — неисправность силовой части;
Ошибка F71 (error F71) — ошибка связи;
Ошибка F80 (error F80) — ошибка автонастройки;
Ошибка F81 (error F81) — ошибка связи RS485;
Ошибка F100 (error F100) — ошибка контрольной суммы записанных параметров;
Ошибка F122 (error F122) — ошибка платы ввода-вывода.

Контактная информация

Время выполнения запроса: 0,00205111503601 секунды.

Old
January 10th, 2017, 09:53 AM

 
#1

Lifetime Supporting Member

United States

Lunatech is offline

 

Join Date: Sep 2009

Location: Midwest

Posts: 9

Question
Powerflex 525 getting random F059 Faults


Hello Everyone,
I have an application using a 525 on ethernet and the safe torque off wired through an Allen Bradley CAT3 Safety Circuit. The S+, S1 and S2 are wired through a 330P output module. I keep getting random F059 Faults, but the 330P output module is not dropping out. There seems to be very little documentation on this fault. Has anyone seen similar problems with this drive/fault? Any help much appreciated!

Reply With Quote

Old
January 10th, 2017, 10:13 AM

 
#2

Lifetime Supporting Member

United States

Robobob is offline

 

Robobob's Avatar

 

Join Date: Apr 2004

Location: Toledo

Posts: 280

Be sure you ave a good connection to the 0vdc side of your 24VDC power supply to the drive. Terminal 4 should be connected to 0VDC. This has solved similar problems I have had with the PF525s in the past.

Reply With Quote

Old
January 10th, 2017, 11:26 AM

 
#3

Lifetime Supporting Member

United States

swimmy67 is offline

 

swimmy67's Avatar

 

Join Date: Apr 2004

Location: Rockford, Illinois area.

Posts: 88

What I have found when using the PF525, I sent a Reset Fault through EthernetIP when the Safe Off was tripped. There is no automatic fault reset for this. You can wire in a fault reset push button or reset from the face of the VFD.

I use the EthernetIP to monitor the VFD and initialize when first powering up and recovering from an E-Stop condition. I use messages to send a Stop to the VFD then Clear Faults when the E-Stop condition has been removed.

Reply With Quote

Old
January 10th, 2017, 11:32 AM

 
#4

Lifetime Supporting Member

United States

dmroeder is offline

 

dmroeder's Avatar

 

Join Date: Apr 2006

Location: Vancouver, WA

Posts: 3,341

When the safety is dropped out on S1 and S2, the default is to throw up that fault.

You can set T105 to 1 (Safety Open En) and it will stop giving that as a fault. So whenever you e-stop the machine (or remove 24V from the safety terminals) it will no longer give you a F059 fault.

Reply With Quote

Old
January 10th, 2017, 02:27 PM

 
#5

Lifetime Supporting Member

United States

Lunatech is offline

 

Join Date: Sep 2009

Location: Midwest

Posts: 9

Thanks RoboBob, I set T105 to 1 and within a few minutes got an F114 fault, but I think I may have caused the microprocessor fault in the way I changed the parameter. I think I will install the factory jumper across the S+, S1 and S2 terminals to isolate the safety relay circuit. If I still get F059, it is most certainly internal to the drive.

Reply With Quote

Old
January 10th, 2017, 03:20 PM

 
#6

Lifetime Supporting Member

United States

Lunatech is offline

 

Join Date: Sep 2009

Location: Midwest

Posts: 9

Apologies dmroeder, I meant to reply to your post concerning T105 parameter.

Reply With Quote

Old
January 10th, 2017, 03:28 PM

 
#7

Lifetime Supporting Member

United States

Lunatech is offline

 

Join Date: Sep 2009

Location: Midwest

Posts: 9

Thanks RoboBob, The only physical wiring on this drive other than power conductors is a jumper from 1-11, 3 safe off connections and relay R5 and R6. All other controls are communicated across ethernet.

Reply With Quote

Old
January 10th, 2017, 03:40 PM

 
#8

Lifetime Supporting Member

United States

Lunatech is offline

 

Join Date: Sep 2009

Location: Midwest

Posts: 9

Thanks Swimmy67,
That’s a good idea to issue a stop / clear fault after an E-Stop condition. We are using an AOI for drive control, might be worth incorporating that message instruction into it.

Reply With Quote

Old
March 30th, 2017, 09:22 AM

 
#9

Member

United States

kurtzberger is offline

 

Join Date: Jul 2014

Location: Westminster, CO

Posts: 10

Has anyone found a solution to this? I’ve added the jumper back to the PF525s (between S+, S1, and S2) and the F059 faults are still occuring at random. Do I need to flash new firmware? They are running v5 right now.

Thank in advance.

Reply With Quote

Old
March 30th, 2017, 01:31 PM

 
#10

Member

United States

BlueAltezza is offline

 

Join Date: Nov 2012

Location: Cleveland, OH

Posts: 243

Quote:

Originally Posted by Robobob
View Post

Be sure you ave a good connection to the 0vdc side of your 24VDC power supply to the drive. Terminal 4 should be connected to 0VDC. This has solved similar problems I have had with the PF525s in the past.

This!

The last time I used some 525’s I had a lot of problems with the safe torque off faults and resetting the drives. Once I hooked that common up and set the 105 and 106 parameters life was good.

Kurtz- do you have a 0V connection to pin 4?

Reply With Quote

Old
March 30th, 2017, 02:14 PM

 
#11

Member

United States

kurtzberger is offline

 

Join Date: Jul 2014

Location: Westminster, CO

Posts: 10

Hey Blue,

That’s actually the first thing I checked. Pin 4 has a 0VDC connection.
Turns out our logic was dropping out the start signal to the drive, due to a bouncing input. We put in a debounce timer, and everything is good now.

Thanks so much!

Reply With Quote

Old
March 30th, 2017, 11:55 PM

 
#12

Lifetime Supporting Member

Ireland

Geospark is offline

 

Geospark's Avatar

 

Join Date: Feb 2012

Location: Kildare

Posts: 3,010

For future reference, and to elaborate on Swimmy67’s good advice, it is advisable to monitor the STO contact status bit via datalinks and once the drive’s Safety Function is reset you can then issue a Clear Fault command via the Logic Command word…

559213 — PowerFlex 525: Disabling Parameter T105 [Safety Open En] / F059 Does Not Disable Safety Circuit
Access Level: Everyone

Of course, this is more useful when you are actually using the STO feature. Leaving the STO contact looped out is best when not being used.

Regards,
George

__________________
«A little nonsense now and then is relished by the wisest men«.

Reply With Quote

Ремонт частотного преобразователя Rockwell Automation Allen Bradley Powerflex в Ставрополе

  • Особенности ремонта частотных преобразователей Allen Bradley
  • Программирование, настройка частотного преобразователя Allen Bradley
  • Ошибки частотного преобразователя Allen Bradley
  • Коды ошибок частотного преобразователя Allen Bradley
  • Частотный преобразователь Allen Bradley инструкция на русском, скачать
  • Схемы подключения частотных преобразователей Allen Bradley
  • Ремонт частотных преобразователей Allen Bradley в сервисном центре
  • Как заказать ремонт частотного преобразователя Allen Bradley

Ремонт частотного преобразователея Rockwell Automation Allen Bradley Powerflex

Ремонт частотного преобразователя Rockwell Automation Allen Bradley Powerflex известного американского производителя промышленной электроники, впрочем, как и ремонт частотников выпущенными под другими брендами имеет ряд особенностей в силу своего конструктива. Частотные преобразователи, точнее их начинка делятся на две части:

  1. Аппаратная часть,
  2. Программная часть.

Приводы данного производителя не являются исключением из правил, именно поэтому ремонт частотного преобразователя Allen Bradley имеет точно такой же ряд особенностей, как и у других преобразователей.

Диагностировать ту или иную неисправность помогают коды ошибок частотного преобразователя, которые отображаются на небольшом дисплее, расположенном на лицевой панели частотника.

Ремонт частотных преобразователей Rockwell Automation Allen Bradley Powerflex, впрочем, как и любых других частотников выпущенных под другими брендами всегда начинается с аппаратной части, после успешного ремонта аппаратной части наступает очередь программной.

Настройка частотного преобразователя Allen Bradley прописана в инструкции завода производителя, для каждой серии частотных преобразователей настройка будет индивидуальной, так как каждая линейка преобразователей решает свои собственные задачи, этим обусловливается широкая номенклатура данного промышленного оборудования. Но все же есть определенная последовательность настройки привода, которая относится ко всем частотным преобразователям, любого бренда.

Программирование, настройка частотного преобразователя Allen Bradley

Программирование частотных преобразователей Rockwell Automation Allen Bradley Powerflex (настройка) происходит в рамках установленных производителем правил, существует общий алгоритм по настройке (программированию частотных преобразователей), который относится ко всем производителям данного промышленного оборудования. Ниже представлена пошаговая инструкция по настройке частотных преобразователей Allen Bradley и подобного промышленного оборудования других брендов.

Ремонт частотного преобразователея Rockwell Automation Allen Bradley Powerflex

  1. Выбор режима управления приводом (управление по показанию датчиков, дистанционное управление, дистанционное управление).
  2. В случае использования отдельного (выносного) монитора, настраивается вывод на него технической информации.
  3. Далее определяем конфигурацию подключения серводвигателя. На данной стадии задаются такие параметры как- возможность применения обратной связи либо без ее применения, а в память блока заносятся данные по: величине крутящего момента, мощности потребителей, номинальное значения частоты, напряжение, ток и скорости вращения ротора.
  4. Программируется минимально допустимая величина напряжения и частоты, а также время ускорения ротора от ноля до номинального значения.
  5. И в завершении, в программу управления частотным преобразователем Allen Bradley вносятся функциональные данные со значениями отдельных клемм и особенностями сигналов. Отмечаются действия оборудования, выполняющиеся автоматически при отсутствии информации поступающей в оперативном режиме с датчика.

В некоторых преобразователях частоты существует пункт наличия/отсутствия фильтра в цепи питания двигателя. Этот пункт отвечает за подключение различных видов нагрузок, в том случае, когда возможно выбрать нормальное или инверсное изменение частоты при повышении уровня сигнала обратной связи.

Ошибки частотного преобразователя Allen Bradley

Ремонт частотных преобразователей Rockwell Automation Allen Bradley Powerflex

В процессе работы выходит из строя даже самое надежное промышленное оборудование. Частотники в наше время, нашли широкое применение абсолютно во всех сферах промышленности, управляя как мини моторами в оргтехнике, так и гигантскими двигателями в горнодобывающей промышленности.

Для простоты общения со столь сложной электроникой все частотные преобразователи оснащены небольшими дисплеями с помощью которых выводятся информационные сообщения с кодами ошибок, расшифровав которые можно сразу же узнать причину ее возникновения. Если учесть распространенность данной промышленной электроники, то появляется острая нужда в расшифровке кодов ошибок частотных преобразователей. В этой статье мы рассмотрим одного из самых известных производителей промышленной электроники имеющему уважение во всем мире, Rockwell Automation Allen Bradley и серию частотных преобразователей Powerflex 520.

Существует несколько видов ошибок, некоторые из них можно устранить автоматически, а некоторые возможно исправить только, обратившись в специализированный сервисный центр. В руководстве пользователя прописаны все коды ошибок частотного преобразователя Rockwell Automation Allen Bradley Powerflex 520 и их расшифровка.

Коды ошибок частотного преобразователя Allen Bradley Powerflex 520

Ошибка – это условие, останавливающее преобразователь. Существует два типа аварий.

Тип Ошибка Описание
1 С автоматическим сбросом/запуском Если произошла ошибка этого типа, а для параметра A541 [Auto Rstrt Tries] установлено значение больше «0», запускается настраиваемый пользователем таймер A542 [Auto Rstrt Delay]. Когда таймер достигает нуля, преобразователь предпринимает попытку автоматического сброса ошибки. И в том случае, если условия, вызвавшего ошибку, больше не существует, произойдёт сброс ошибки и преобразователь снова будет запущен.
2 Несбрасываемая Этот тип ошибки может потребовать ремонта преобразователя или двигателя, он может быть вызван неправильным подключением кабелей или допущенными в программе ошибками. Для сброса ошибки необходимо устранить её причину.
Поз. Ошибка Тип Описание
F000 Нет ошибки Ошибка отсутствует.
F002 Дополнительный вход 1 Вход внешнего отключения (вспом.).
F003 Потеря питания 2 В однофазном режиме обнаружена чрезмерная нагрузка.
F004 Пониженное напряжение 1 Напряжение шины постоянного тока упало ниже минимального значения.
F005 Перенапряжение 1 Напряжение на шине постоянного тока превышает максимальное значение.
F006 Двигатель заблокирован 1 Преобразователь не подходит для разгона или торможения двигателя.
F007 Перегрузка двигателя 1 Сработал встроенный электронный ограничитель нагрузки.
F008 Перегрев радиатора 1 Температура радиатора/модуля питания вышла за пределы допуска.
F009 Перегрев контр.узла 1 Температура модуля управления превышает заданное значение.
F012 Превышение аппаратного тока 2 Выходной ток преобразователя превысил допустимый предел.
F013 Ошибка заземления 2 Обнаружено замыкание на землю одной или нескольких выходных клемм преобразователя.
F015(1) Потеря нагрузки 2 Выходной ток крутящего момента ниже значения, установленного параметром A490 [Load Loss Level], в течение времени, превышающего установленное параметром A491 [Load Loss Time].
F021 Обрыв фазы вывода 1 Обрыв фазы вывода (если включена). Настраивается при помощи A557 [Out Phas Loss En].
F029 Обрыв аналог. ввода 1 Для аналогового входа задано сообщение об ошибке в случае пропадания сигнала. Пропал сигнал. Настраивается при помощи t094 [Anlg In V Loss] или t097 [Anlg In mA Loss].
F033 Попытки авт. перезапуска 2 Предпринятые преобразователем попытки сброса ошибки и продолжения работы оканчивались неудачей столько раз, сколько было задано в параметре A541 [Auto Rstrt Tries].
F038
F039
F040
Фаза U на землю
Фаза V на землю
Фаза W на землю
2 Ошибка замыкания фазы на землю была обнаружена между преобразователем и двигателем в этой фазе.
F041
F042
F043
Короткое замыкание фаз U и V
Короткое замыкание фаз U и W
Короткое замыкание фаз V и W
2 Между двумя данными клеммами обнаружено превышение по току.
F048 Запись в параметры значений по умолчанию 1 Преобразователь подал команду записи в ЭППЗУ значений по умолчанию.
F059(1) Откр.безопасн. 1 Отключены оба защитных входа (Safety 1, Safety 2). Настраивается при помощи t105 [Safety Open En].
F063 Превышение по току 1 Запрограммированное значение A486, A488 [Shear Pinx Level] превышено на период, превышающий время, заданное в A487, A489 [Shear Pin x Time].
F064 Перегрузка преобразователя 2 Превышена допустимая перегрузка преобразователя.
F070 Блок питания 2 Обнаружена ошибка питания преобразователя.
F071 Потеря сети DSI 2 Управление по Modbus или каналу связи DSI прервано.
F072 Потеря сети Opt 2 Управление по удалённой сети платы выбора подключений прервано.
F073(1) Потеря сети EN 2 Управление через встроенный адаптер EtherNet/IP прервано.
F080 Ошибка автоподстройки 2 Произошла ошибка функции автонастройки или работа функции отменена пользователем.
F081 Потеря DSI Comm 2 Связь между преобразователем и ведущим устройством Modbus или DSI прервана.
F082 Потеря Opt Comm 2 Связь между преобразователем и сетевой платой выбора подключений прервана.
F083(1) Потеря EN Comm 2 Внутренняя связь между преобразователем и встроенным адаптером EtherNet/IP прервана.
F091(1) Потеря энкодера 2 Необходим дифференциальный энкодер. Отсутствует сигнал в одном из двух каналов энкодера.
F094 Потеря функции 2 Вход «Замораживание-запуск» (потеря функции) не активен, вход к программируемой клемме открыт.
F100 Ошибка контрольной суммы параметра 2 Энергонезависимая память параметров преобразователя повреждена.
F101 Внешняя память 2 Внешняя энергонезависимая память повреждена.
F105 Ошибка соед. контр. узла 2 Модуль управления отсоединён во время включения преобразователя.
F106 Несовместим. контр. уз. – блок пит. 2 Модуль управления не может распознать модуль питания.
F107 Замен. контр. уз. – блок пит. 2 Модуль управления установлен на модуль питания с отличающейся номинальной мощностью.
F109 Несоотв. контр. уз. – блок пит. 2 Модуль управления установлен на модуль питания с отличающейся номинальной мощностью.
F110 Мембранная клавиатура 2 Ошибка/отсоединение мембранной клавиатуры.
F111(1) Защитное оборудование 2 Аппаратная ошибка включения защитного оборудования. Один из защитных входов не включён.
F114 Сбой микропроц. 2 Сбой микропроцессора
F122 Ошибка платы ввода-вывода 2 Обнаружен сбой в секции ввода- вывода и управления преобразователя.
F125 Требуется обновление флеш-памяти 2 Встроенное ПО в преобразователе повреждено, не согласовано или несовместимо с аппаратурой.
F126 NonRecoverablErr 2 Была обнаружена неустранимая ошибка встроенного ПО или аппаратуры. Преобразователь был автоматически остановлен и выполнен сброс.
F127 DSIFlashUpdatReq 2 Была обнаружена существенная проблема со встроенным ПО, и преобразователь работает с использованием резервного встроенного ПО, которое поддерживает только связь DSI.

(1) Эта ошибка неприменима к преобразователям PowerFlex 523.

Частотный преобразователь Allen Bradley инструкция на русском, скачать

Все настройки частотных преобразователей Rockwell Automation Allen Bradley Powerflex приведены в технической документации ниже в удобном формате (PDF) который можно скачать на свой компьютер, распечатать или просто открыть на нашем сайте.

Промышленный частотный преобразователь Allen Bradley инструкции, скачать русскоязычные и англоязычные версии в формате PDF.

Частотный преобразователь Allen Bradley PowerFlex 4 инструкция

podkategorij Скачать PDF

Частотный преобразователь Allen Bradley PowerFlex 4M инструкция

podkategorij Скачать PDF

Частотный преобразователь Allen Bradley PowerFlex 40 инструкция

podkategorij Скачать PDF

Частотный преобразователь Allen Bradley PowerFlex 40P инструкция

podkategorij Скачать PDF

Частотный преобразователь Allen Bradley PowerFlex 70 инструкция

podkategorij Скачать PDF

Частотный преобразователь Allen Bradley PowerFlex 400 инструкция

podkategorij Скачать PDF

Частотный преобразователь Allen Bradley PowerFlex 520 инструкция на руссокм

podkategorij Скачать PDF

Частотный преобразователь Allen Bradley PowerFlex 520 технические характеристики на русском

podkategorij Скачать PDF

Частотный преобразователь Allen Bradley PowerFlex 700AFE инструкция на русском

podkategorij Скачать PDF

Частотный преобразователь Allen Bradley PowerFlex 700L инструкция

podkategorij Скачать PDF

Частотный преобразователь Allen Bradley PowerFlex 700 инструкция на русском

podkategorij Скачать PDF

Частотный преобразователь Allen Bradley PowerFlex 750 инструкция на русском

podkategorij Скачать PDF

Частотный преобразователь Allen Bradley PowerFlex 750 инструкция по монтажу на русском

podkategorij Скачать PDF

Частотный преобразователь Allen Bradley PowerFlex-750 инструкция по программированию на русском

podkategorij Скачать PDF

Схемы подключения частотных преобразователей Allen Bradley

Схемы подключений частотных преобразователей Allen Bradley могут отличатся друг от друга даже если эти преобразователи относятся ко одной линейке. Схема подключения преобразователя зависит от потребляемой частотным преобразователем нагрузки или питающей сети к которой подключается частотник 200V – 380V, а также от оборудования с которым предполагается работа данного частотника.

Ниже приведены схемы подключения частотного преобразователя Allen Bradley.

Схема подключения частотного преобразователя Allen Bradley PowerFlex-4

Схема подключения частотного преобразователя Allen Bradley PowerFlex-4M

Схема подключения частотного преобразователя Allen Bradley PowerFlex 4

Схема подключения частотного преобразователя Allen Bradley PowerFlex 4M

Схема подключения частотного преобразователя Allen Bradley PowerFlex-40

Схема подключения частотного преобразователя Allen Bradley PowerFlex 40

Ремонт частотных преобразователей Allen Bradley в сервисном центре

Ремонт частотного преобразователея Rockwell Automation Allen Bradley Powerflex

Сервисный центр «Кернел» производит ремонт частотных преобразователей Rockwell Automation Allen Bradley Powerflex в Ставрополе с 2002 года. За время существования компании наши сотрудники накопили колоссальный опыт в ремонте преобразователей частоты такого известного производителя как Ален Бредли. Ремонт подобного промышленного оборудования ответственное и сложное занятие, требующие максимальной отдачи, профессионализма и максимально полной материальной базе.

Специалисты нашего сервисного центра максимальное внимание уделяют качеству исполнения ремонта, программирования и настройке промышленных преобразователей частоты, не зависимо от производителя данного промышленного оборудования. Именно поэтому мы смело даем гарантию на ремонт частотных преобразователей Rockwell Automation Allen Bradley Powerflex и запасные части замененные в процессе ремонта шесть месяцев.

Ремонт частотных преобразователей Allen Bradley в Ставрополе производится исключительно с использованием оригинальных запасных частей, на компонентном уровне с применением высокотехнологичного оборудования, квалифицированным персоналом с инженерным образованием.

Мы ремонтируем все линейки частотных преобразователей Allen Bradley в том числе:

Серия ПЧ Типы частотных преобразователей Rockwell Automation Allen Bradley Powerflex
PowerFlex 755 20G11GD2P1JA0NNNNN; 20G11GD3P4JA0NNNNN; 20G11GD5P0JA0NNNNN; 20G11GD8P0JA0NNNNN; 20G11GD011JA0NNNNN; 20G11GD014JA0NNNNN; 20G11GD022JA0NNNNN; 20G11GD027JA0NNNNN; 20G11GD034JA0NNNNN; 20G11GD040JA0NNNNN; 20G11GD052JA0NNNNN; 20G11GD065JA0NNNNN; 20G11GD077JA0NNNNN; 20G1AJD430JN0NNNNN; 20G1AJD485JN0NNNNN; 20G1AJD545JN0NNNNN; 20G1AJD617JN0NNNNN; 20G1AJD710JN0NNNNN; 20G1AJD740JN0NNNNN; 20G11JD800JN0NNNNN; 20G11JD960JN0NNNNN; 20G11JD1K0JN0NNNNN; 20G11JD1K2JN0NNNNN; 20G11JD1K3JN0NNNNN; 20G11JD1K4JN0NNNNN; 20G11JD1K5JN0NNNNN; 20G11JD2K0JN0NNNNN; 20G11RB2P2JA0NNNNN; 20G11RB4P2JA0NNNNN; 20G11RB6P8JA0NNNNN; 20G11RB9P6JA0NNNNN; 20G11RB015JA0NNNNN; 20G11NB2P2JA0NNNNN; 20G11NB4P2JA0NNNNN; 20G11NB6P8JA0NNNNN; 20G11NB9P6JA0NNNNN; 20G11NB015JA0NNNNN; 20G11NB022JA0NNNNN; 20G11NB028JA0NNNNN; 20G11NB042JA0NNNNN; 20G11NB054JA0NNNNN; 20G11NB070JA0NNNNN; 20G11NB080JA0NNNNN
PowerFlex 753 20F11RB2P2JA0NNNNN; 20F11RB4P2JA0NNNNN; 20F11RB6P8JA0NNNNN; 20F11RB9P6JA0NNNNN; 20F11RB015JA0NNNNN; 20F11NB2P2JA0NNNNN; 20F11NB4P2JA0NNNNN; 20F11NB6P8JA0NNNNN; 20F11NB9P6JA0NNNNN; 20F11NB015JA0NNNNN; 20F11NB022JA0NNNNN; 20F11NB028JA0NNNNN; 20F11NB042JA0NNNNN; 20F11NB054JA0NNNNN; 20F11NB070JA0NNNNN; 20F11NB080JA0NNNNN; 20F11GB2P2JA0NNNNN; 20F11GB4P2JA0NNNNN; 20F11GB6P8JA0NNNNN; 20F11GB9P6JA0NNNNN; 20F11GB015JA0NNNNN; 20F11GB022JA0NNNNN; 20F11GB028JA0NNNNN; 20F11GB042JA0NNNNN; 20F11GB054JA0NNNNN; 20F11GB070JA0NNNNN; 20F11FB2P2JA0NNNNN; 20F11FB4P2JA0NNNNN; 20F11FB6P8JA0NNNNN; 20F11FB9P6JA0NNNNN; 20F11FB015JA0NNNNN; 20F11FB022JA0NNNNN; 20F11FB028JA0NNNNN; 20F11FB042JA0NNNNN; 20F11FB054JA0NNNNN; 20F11FB070JA0NNNNN; 20F11FB080JA0NNNNN
PowerFlex 755TL
PowerFlex 755TR
PowerFlex 755TM
20G1xxC302xNxNNNNN-Cx-Px; 20G1xxC367xNxNNNNN-Cx-Px; 20G1xxC460xNxNNNNN-Cx-Px; 20G1xxC540xNxNNNNN-Cx-Px; 20G1xxC585xNxNNNNN-Cx-Px; 20G1xxC650xNxNNNNN-Cx-Px; 20G1xxC750xNxNNNNN-Cx-Px; 20G1xxC770xNxNNNNN-Cx-Px; 20G1xxC920xNxNNNNN-Cx-Px; 20G1xxC1K0xNxNNNNN-Cx-Px; 20G1xxC1K1xNxNNNNN-Cx-Px; 20G1xxD302xNxNNNNN-Cx-Px; 20G1xxD505xNxNNNNN-Cx-Px; 20G1xxD710xNxNNNNN-Cx-Px; 20G1xxD960xNxNNNNN-Cx-Px; 20G1xxD1K3xNxNNNNN-Cx-Px; 20G1xxD1K6xNxNNNNN-Cx-Px; 20G1xxD2K6xNxNNNNN-Cx-Px; 20G1xxD3K4xNxNNNNN-Cx-Px; 20G1xxE242xNxNNNNN-Cx-Px; 20G1xxE295xNxNNNNN-Cx-Px; 20G1xxE435xNxNNNNN-Cx-Px; 20G1xxE690xNxNNNNN-Cx-Px; 20G1xxE980xNxNNNNN-Cx-Px; 20G1xxE1K2xNxNNNNN-Cx-Px; 20G1xxE2K4xNxNNNNN-Cx-Px; 20G1xxF215xNxNNNNN-Cx-Px; 20G1xxF330xNxNNNNN-Cx-Px; 20G1xxF415xNxNNNNN-Cx-Px; 20G1xxF650xNxNNNNN-Cx-Px; 20G1xxF920xNxNNNNN-Cx-Px; 20G1xxF1K4xNxNNNNN-Cx-Px; 20G1xxF1K8xNxNNNNN-Cx-Px; 20G1xxF2K3xNxNNNNN-Cx-Px;
PowerFlex 70 20AB2P2A0AYNNNC0; 20AB2P2A0AYNANC0; 20AB4P2A0AYNNNC0; 20AB4P2A0AYNANC0; 20AB6P8A0AYNNNC0; 20AB6P8A0AYNANC0; 20AB9P6A0AYNNNC0; 20AB9P6A0AYNANC0; 20AB015A0AYNANC0; 20AB022A0AYNANC0; 20AB028A0AYNANC0; 20AB042A0AYNANC0; 20AB054A0AYNANC0; 20AB070A0AYNANC0; 20AC1P3A0AYNNNC0; 20AC1P3A0AYNANC0; 20AC2P1A0AYNNNC0; 20AC2P1A0AYNANC0; 20AC3P5A0AYNNNC0; 20AC3P5A0AYNANC0; 20AC5P0A0AYNNNC0; 20AC5P0A0AYNANC0; 20AC8P7A0AYNNNC0; 20AC8P7A0AYNANC0; 20AC011A0AYNANC0; 20AC015A0AYNANC0; 20AC043A0AYNANC0; 20AE0P9A0AYNNNC0; 20AE3P9A0AYNNNC0; 20AE011A0AYNNNC0; 20AE022A0AYNNNC0; 20AE041A0AYNANC0; 20AB2P2C3AYNNNC0; 20AB022C3AYNANC0; 20AB070C3AYNANC0; 20AC2P1C3AYNNNC0; 20AD2P1C3AYNANC0; 20AD011C3AYNANC0; 20AC037C3AYNANC0; 20AD052C3AYNANC0; 20AC072C3AYNANC0
PowerFlex 523 25A-V1P6N104; 25A-V2P5N104; 25A-V4P8N104; 25A-V6P0N104; 25A-A1P6N104; 25A-A1P6N114; 25A-A2P5N104; 25A-A2P5N114; 25A-A4P8N104; 25A-A4P8N114; 25A-A8P0N104; 25A-A8P0N114; 25A-A011N104; 25A-A011N114; 25A-B1P6N104; 25A-B2P5N104; 25A-B5P0N104; 25A-B8P0N104; 25A-B011N104; 25A-B017N104; 25A-B024N104; 25A-B032N104; 25A-B048N104; 25A-B062N104; 25A-D1P4N104; 25A-D2P3N114; 25A-D4P0N104; 25A-D6P0N114; 25A-D010N104; 25A-D013N114; 25A-D017N104; 25A-D024N114; 25A-D030N104; 25A-D037N114; 25A-E0P9N104; 25A-E1P7N104; 25A-E3P0N104; 25A-E4P2N104; 25A-E6P6N104; 25A-E9P9N104; 25A-E012N104; 25A-E019N104; 25A-E022N104; 25A-E027N104; 25A-E032N104
PowerFlex 525 25B-V2P5N104; 25B-V4P8N104; 25B-V6P0N104; 25B-A2P5N104; 25B-A2P5N114; 25B-A4P8N104; 25B-A4P8N114; 25B-A8P0N104; 25B-A8P0N114; 25B-A011N104; 25B-A011N114; 25B-B2P5N104; 25B-B5P0N104; 25B-B8P0N104; 25B-B011N104; 25B-B017N104; 25B-B024N104; 25B-B032N104; 25B-B048N104; 25B-B062N104; 25B-D1P4N104; 25B-D2P3N114; 25B-D4P0N104; 25B-D6P0N114; 25B-D010N104; 25B-D013N114; 25B-D017N104; 25B-D024N114; 25B-D030N104; 25B-D037N114; 25B-E0P9N104; 25B-E1P7N104; 25B-E3P0N104; 25B-E4P2N104; 25B-E6P6N104; 25B-E9P9N104; 25B-E012N104; 25B-E022N104; 25B-E032N104
PowerFlex 527 25C-V2P5N104; 25C-V4P8N104; 25C-V6P0N104; 25C-A2P5N104; 25C-A4P8N104; 25C-A8P0N104; 25C-A011N104; 25C-A2P5N114; 25C-A4P8N114; 25C-A8P0N114; 25C-A011N114; 25C-B2P5N104; 25C-B5P0N104; 25C-B8P0N104; 25C-B011N104; 25C-B017N104; 25C-B024N104; 25C-B032N104; 25C-B048N104; 25C-B062N104; 25C-D1P4N104; 25C-D2P3N104; 25C-D4P0N104; 25C-D6P0N104; 25C-D010N104; 25C-D013N104; 25C-D017N104; 25C-D024N104; 25C-D030N104; 25C-D1P4N114; 25C-D2P3N114; 25C-D4P0N114; 25C-D6P0N114; 25C-D010N114; 25C-D013N114; 25C-D017N114; 25C-D024N114; 25C-D030N114; 25C-D037N114; 25C-D043N114; 25C-E0P9N104; 25C-E1P7N104; 25C-E3P0N104; 25C-E4P2N104; 25C-E6P6N104; 25C-E9P9N104; 25C-E012N104; 25C-E019N104; 25C-E022N104; 25C-E027N104; 25C-E032N104
PowerFlex 4M 22F-V1P6N103; 22F-V2P5N103; 22F-V4P5N103; 22F-V6P0N103; 22F-A1P6N103; 22F-A1P6N113; 22F-A2P5N103; 22F-A2P5N113; 22F-A4P2N103; 22F-A4P2N113; 22F-A8P0N103; 22F-A8P0N113; 22F-A011N103; 22F-A011N113; 22F-B1P6N103; 22F-B2P5N103; 22F-B4P2N103; 22F-B8P0N103; 22F-B012N103; 22F-B017N103; 22F-B025N104; 22F-B033N104; 22F-D1P5N103; 22F-D1P5N113; 22F-D2P5N103; 22F-D2P5N113; 22F-D4P2N103; 22F-D4P2N113; 22F-D6P0N103; 22F-D6P0N113; 22F-D8P7N103; 22F-D8P7N113; 22F-D013N104; 22F-D013N114; 22F-D018N104; 22F-D018N114; 22F-D024N104; 22F-D024N114
PowerFlex 400 22C-B012N103; 22C-B012F103; 22C-B017N103; 22C-B017F103; 22C-B024N103; 22C-B024F103; 22C-B033N103; 22C-B033F103; 22C-B049A103; 22C-B065A103; 22C-B075A103; 22C-B090A103; 22C-B120A103; 22C-B145A103; 22C-D6P0N103; 22C-D6P0F103; 22C-D010N103; 22C-D010F103; 22C-D012N103; 22C-D012F103; 22C-D017N103; 22C-D017F103; 22C-D022N103; 22C-D022F103; 22C-D030N103; 22C-D030F103; 22C-D038A103; 22C-D045A103; 22C-D060A103; 22C-D072A103; 22C-D088A103; 22C-D105A103; 22C-D142A103; 22C-D170A103; 22C-D208A103; 22C-D260A103; 22C-D310A103; 22C-D370A103; 22C-D460A103
PowerFlex 4 22A-V1P5N104; 22A-V2P3N104; 22A-V4P5N104; 22A-V6P0N104; 22A-A1P4N103; 22A-A2P1N103; 22A-A3P6N103; 22A-A6P8N103; 22A-A9P6N103; 22A-A1P4N113; 22A-A2P1N113; 22A-A3P6N113; 22A-A6P8N113; 22A-A9P6N113; 22A-A1P5N114; 22A-A2P3N114; 22A-A4P5N114; 22A-A8P0N114; 22A-A1P5N104; 22A-A2P3N104; 22A-A4P5N104; 22A-A8P0N104; 22A-B1P5N104; 22A-B2P3N104; 22A-B4P5N104; 22A-B8P0N104; 22A-B012N104; 22A-B017N104; 22A-D1P4N104; 22A-D2P3N104; 22A-D4P0N104; 22A-D6P0N104; 22A-D8P7N104; 22B-A2P3N114
PowerFlex 40 22B-V2P3N104; 22B-V5P0N104; 22B-V6P0N104; 22B-A5P0N114; 22B-A8P0N114; 22B-A012N114; 22B-A2P3N104; 22B-A5P0N104; 22B-A8P0N104; 22B-A012N104; 22B-B2P3N104; 22B-B5P0N104; 22B-B8P0N104; 22B-B012N104; 22B-B017N104; 22B-B024N104; 22B-B033N104; 22B-D1P4N104; 22B-D2P3N104; 22B-D4P0N104; 22B-D6P0N104; 22B-D010N104; 22B-D012N104; 22B-D017N104; 22B-D024N104; 22B-E1P7N104; 22B-E3P0N104; 22B-E4P2N104; 22B-E6P6N104; 22B-E9P9N104; 22B-E012N104; 22B-E019N104
PowerFlex 40P 22D-B2P3N104; 22D-B5P0N104; 22D-B8P0N104; 22D-B012N104; 22D-B017N104; 22D-B024N104; 22D-B033N104; 22D-B2P3H204; 22D-B5P0H204; 22D-B8P0H204; 22D-B012H204; 22D-B017H204; 22D-B024H204; 22D-B033H204; 22D-B2P3F104; 22D-B5P0F104; 22D-B8P0F104; 22D-B012F104; 22D-B017F104; 22D-B024F104; 22D-B033F104; 22D-D1P4N104; 22D-D2P3N104; 22D-D4P0N104; 22D-D6P0N104; 22D-D010N104; 22D-D012N104; 22D-D017N104; 22D-D024N104; 22D-D1P4F104; 22D-D2P3F104; 22D-D4P0F104; 22D-D6P0F104; 22D-D010F104; 22D-D012F104; 22D-D017F104; 22D-D024F104; 22D-E1P7H204; 22D-E3P0H204; 22D-E4P2H204; 22D-E6P6H204; 22D-E9P9H204; 22D-E012H204; 22D-E019H204
PowerFlex 700 20BD011A3AYYADB0; 20BD8P0A3AYYAEB0; 20BD011A3NYNAED0; 20BD156A3ANNAED0; 20BC011A3AYYANC1; 20BD248A3AYNANC0; 20BH105A3AYNANA0; 20BD180A3ANNACB0; 20BC037A3AYNACA0; 20BE144A3AYNACD0; 20BC205A3ANNAEC0; 20BR156F0ANNAND0; 20BB015A3AYNBNB0; 20BD8P0A3NYNACD1; 20BB154A3ANNANB0; 20BB015A3AYNBEC0NNAD; 20BD077A3NYNANC0; 20BD180A3AYNACD0; 20BD8P0A3AYYACB0; 20BD8P0A3NYYAND0; 20BD180A3ANNADD1; 20BC022A3AYNANC1; 20BR180A3ANNANA0; 20BD125A3AYNAEB0; 20BE125A3ANNADD0; 20BR248A3AYNACC1; 20BE125A3ANNAND0; 20BC125A3ANNACA0; 20BC170A3NYNAEA0; 20BP105A3ANNAEC1; 20BP140F3ANNANC0; 20BD180A3ANNANC0NNAD; 20BP205A3ANNADC1; 20BD248A3ANNAEA0; 20BB154A3ANNACB0; 20BD8P0A3NYNADB0; 20BD125A3AYNAND0; 20BD248A3ANNAEB0; 20BD180A3ANNADD0; 20BD156A0NYNACC0
PowerFlex 700S 20DB015A3EYNACGNE; 20DD5P0A3NYYACGNE; 20DB022A3EYNACGNE; 20DB042A3EYNACGNE; 20DD077A3EYNANASE; 20DD3P4A3EYNACASE; 20DD180A3EYNAEASE; 20DC3P5A3EYNAEBSE; 20DR180A3NNNACHNE; 20DD027A3NYNANANE; 20DD052A3NYNANANE; 20DB4P2A0EYNANANE; 20DD5P0A3EYNAEBNE; 20DC037A0NYNANANE; 20DR156A0NNNACGNE; 20DD077A3EYNANDNK; 20DD052A0NYNANANE; 20DD027A0EYNANGNE; 20DD014A3NYYACBSE; 20DD034A0EYYANANE; 20DC8P7A0NYNANCNK; 20DR125A3ENNACASE; 20DD248A3ENNANGNE; 20DD027A3EYNACGNE; 20DD065A0NYNANANK; 20DH300N0ENNBNANK; 20LF705N0QNNJNB0KA; 20DD261A3EYNBEASE; 20DD156A0EYNACASE; 20DR125A0ENNACANE
PowerFlex 700L 21LC1K2N0NNNTEZ0WA; 20LD650N3ENNEEASEA; 20LD650ACENNACA0EA; 20LC1K2ACENNAN10WA; 20LD1K2ACENNAEA0EA; 20LD650A0NNNANBSEA; 20LD1K2ACENNANDSLA; 20LC1K2N0QNNJNC0LA; 20LF380N0QNNEND0LA; 20LD650ACENNAND0LA; 20LD650N0QNNENA0LA; 20LD360N3ENNADDCLA; 20LD650N0QNNEND0LA; 20LD650ACENNA2CSLA; 20LF380N3ENNLNCBLA; 20LD650A0ENNANA0EA; 20LD650N0NNNLEBSEA; 20LC180N3ENNACBAEABB; 20LE425N0QNNENA0LA; 20LF705N0QNNJNA0LA; 20LD650ACENNACABEA; 20LF380N0QNNENB0LA; 20LD1K2N0QNNJND0LA; 20LD650A0ENNAND0LA; 20LE425N0ENNLNASEA; 20LD1K2N0ENNJNASEA; 20LC1K2N0QNNJND0LA; 20LF380N0QNNENA0LA; 20LD360N0ENNANC0LA; 20LD650ACENNA6CSLA

В таблице указаны далеко не все типы частотных преобразователей Rockwell Automation Allen Bradley Powerflex ремонт которых выполняет сервисный центр «Кернел».

В случае выхода из строя преобразователя частоты на вашем производстве либо появились проблемы с приводом, которые вы не можете решить самостоятельно, мы всегда рады вам помочь. Специалисты нашего сервисного центра в минимальные сроки проведут глубокую диагностику с последующим ремонтом частотного преобразователя PowerFlex. Оставьте заказ на ремонт промышленного оборудования используя форму на сайте, либо свяжетесь с нашими менеджерами, сделать это очень просто.

Как заказать ремонт частотного преобразователя Allen Bradley

У вас остались вопросы, связанные с ремонтом частотных преобразователей Allen Bradley? Оставьте заявку на ремонт частотного преобразователя Rockwell Automation Allen Bradley Powerflex в Ставрополе нашим менеджерам. Связаться с ними можно несколькими способами:

  • Заказав обратный звонок (кнопка в правом нижнем углу сайта)
  • Посредством чата (кнопка расположена с левой стороны сайта)
  • Позвонив по номеру телефона: +7(8482) 79-78-54; +7(917) 121-53-01
  • Написав на электронную почту: 89171215301@mail.ru

Далеко не полный список производителей промышленной электроники и оборудования, ремонтируемой в нашей компании.

  • В начало статьи

When your Allen Bradley PowerFlex 525 drive gives trouble, diagnosing the issue and getting the drive back in service quickly can be imperative. Fortunately, most problems with the PowerFlex 525 drive series VFD products can be diagnosed by the fault code indicated on its display.

Below are listed the PowerFlex 525 Fault Codes with fault number, Fault/Alarm Text, description of the fault and possible solutions. For more detailed information, see below for a link to the PowerFlex 525 troubleshooting guide.

Fault Name/Description/Action

  
F000 No Fault
No fault present.
——
F002 Auxiliary Input

External trip (Auxiliary) input.

• Check remote wiring.
• Verify communications programming for intentional fault.

——
F003 Power Loss

Single phase operation detected with excessive load.

• Monitor the incoming AC line for low voltage or line power interruption.
• Check input fuses.

——

F004 UnderVoltage
DC bus voltage fell below the minimum value.

• Monitor the incoming AC line for low voltage or line power interruption.

——

F005 OverVoltage
DC bus voltage exceeded maximum value.

• Monitor the AC line for high line voltage or transient conditions. Bus overvoltage can also be caused by motor regeneration. Extend the decel time or install dynamic brake option.

——

F006 Motor Stalled

Drive is unable to accelerate or decelerate motor.
• Increase P041, A442, A444, A446 [Accel Time x] or reduce load so drive output current does not exceed the current set by parameter A484, A485 [Current Limit x] for too long.

——

F007 Motor Overload
Internal electronic overload trip.

• An excessive motor load exists.
• Reduce load so drive output current does not exceed the current set by parameter P033 [Motor OL Current].
• Verify A530 [Boost Select] setting.

——

F008 Heatsink OvrTmp
Heatsink/Power Module temperature exceeds a predefined value.

• Check for blocked or dirty heat sink fins.

• Verify that ambient temperature has not exceeded the rated ambient temperature.
• Check fan.

——

F009 CC OvrTmp
Control module temperature exceeds a predefined value.

• Check product ambient temperature.
• Check for airflow obstruction.
• Check for dirt or debris.
• Check fan.

——

F012 HW OverCurrent
The drive output current has exceeded the hardware current limit.

• Check programming.

• Check for excess load, improper A530 [Boost Select] setting, DC brake volts set too high or other causes of excess current.

——

F013 Ground Fault
A current path to earth ground has been detected at one or more of the drive output terminals.

• Check the motor and external wiring to the drive output terminals for a grounded condition.

——

F015 Load Loss
The output torque current is below the value programmed in A490 [Load Loss Level] for a time period greater than the time programmed in A491 [Load Loss Time].
• Verify connections between motor and load.
• Verify level and time requirements

——

F021 Output Ph Loss
Output Phase Loss (if enabled).
Configure with A557 [Out Phas Loss En].
• Verify motor wiring.
• Verify motor.

——

F029 Analog In Loss
An analog input is configured to fault on signal loss. A signal loss has occurred. Configure with t094 [Anlg In V Loss] or t097 [Anlg In mA Loss].
• Check for broken/loose connections at inputs.
• Check parameters.

——

F033 Auto Rstrt Tries
Drive unsuccessfully attempted to reset a fault and resume running for the programmed number of A541 [Auto Rstrt Tries].
• Correct the cause of the fault and manually clear.

——

F038 Phase U to Gnd
A phase to ground fault has been detected between the drive and motor in this phase.
• Check the wiring between the drive and motor.
• Check motor for grounded phase.

——

F039 Phase V to Gnd
A phase to ground fault has been detected between the drive and motor in this phase.
• Check the wiring between the drive and motor.
• Check motor for grounded phase.

——

F040 Phase W to Gnd
A phase to ground fault has been detected between the drive and motor in this phase.
• Check the wiring between the drive and motor.
• Check motor for grounded phase.

——

F041 Phase UV Short
Excessive current has been detected between these two output terminals.
• Check the motor and drive output terminal wiring for a shorted condition.

——

F042 Phase UW Short
Excessive current has been detected between these two output terminals.
• Check the motor and drive output terminal wiring for a shorted condition.

——

F043 Phase VW Short
Excessive current has been detected between these two output terminals.
• Check the motor and drive output terminal wiring for a shorted condition.

——

F048 Params Defaulted
The drive was commanded to write default values to EEPROM.
• Clear the fault or cycle power to the drive.
• Program the drive parameters as needed.

——

F059 Safety Open
Both of the safety inputs (Safety 1, Safety 2) are not enabled. Configure with t105 [Safety Open En].
• Check safety input signals. If not using safety, verify and tighten jumper for I/O terminals S1, S2 and S+.

——

F063 SW OverCurrent
Programmed A486, A488 [Shear Pinx Level] has been exceeded for a time period greater than the time programmed in A487, A489 [Shear Pin x Time].
• Verify connections between motor and load.
• Verify level and time requirements.

——

F064 Drive Overload
Drive overload rating has been exceeded.
• Reduce load or extend Accel Time.

——

F070 Power Unit
Failure has been detected in the drive power section.
• Check maximum ambient temperature has not been exceeded.
• Cycle power.
• Replace drive if fault cannot be cleared.

——

F071 DSI Net Loss
Control over the Modbus or DSI communication link has been interrupted.
• Cycle power.
• Check communications cabling.
• Check Modbus or DSI setting.
• Check Modbus or DSI status.

——

F072 Opt Net Loss
Control over the network option card’s remote network has been interrupted.
• Cycle power.
• Check communications cabling.
• Check network adapter setting.
• Check external network status.

——

F073 EN Net Loss
Control through the embedded EtherNet/IP adapter has been interrupted.
• Cycle power.
• Check communications cabling.
• Check EtherNet/IP setting.
• Check external network status.

——

F080 Autotune Failure
The autotune function was either cancelled by the user or failed.
• Restart procedure.

——

F081 DSI Comm Loss
Communications between the drive and the Modbus or DSI master device have been interrupted.
• Cycle power.
• Check communications cabling.
• Check Modbus or DSI setting.
• Check Modbus or DSI status.
• Modify using C125 [Comm Loss Action].
• Connecting I/O terminals C1 and C2 to ground may improve noise immunity.
• Replace wiring, Modbus master device, or control module.

——

F082 Opt Comm Loss
Communications between the drive and the network option card have been interrupted.
• Cycle power.
• Reinstall option card in drive.
• Modify using C125 [Comm Loss Action].
• Replace wiring, port expander, option card, or control module.

——

F083 EN Comm Loss
Internal communications between the drive and the embedded EtherNet/IP adapter have been interrupted.
• Cycle power.
• Check EtherNet/IP setting.
• Check drive’s Ethernet settings and diagnostic parameters.
• Modify using C125 [Comm Loss Action].
• Replace wiring, Ethernet switch, or control module.

——

F091 Encoder Loss
Requires differential encoder. One of the 2 encoder channel signals is missing.
• Check Wiring.
• If P047, P049, P051 [Speed Referencex] = 16 “Positioning” and A535 [Motor Fdbk Type] = 5 “Quad Check”, swap the Encoder channel inputs or swap any two motor leads.
• Replace encoder.

——

F094 Function Loss
“Freeze-Fire” (Function Loss) input is inactive, input to the programmed terminal is open.
• Close input to the terminal and cycle power.

——

F100 Parameter Chksum
Drive parameter non-volatile storage is corrupted.
• Set P053 [Reset To Defalts] to 2 “Factory Rset”.

——

F101 External Storage
External non-volatile storage has failed.
• Set P053 [Reset To Defalts] to 2 “Factory Rset”.

——

F105 C Connect Err
Control module was disconnected while drive was powered.
• Clear fault and verify all parameter settings. Do not remove or install the control module while power is applied.

——

F106 Incompat C-P
The PowerFlex 525 control module does not support power modules with 0.25 HP power rating.
• Change to a different power module.
• Change to a PowerFlex 523 control module.

——

F107 Replaced C-P
The control module could not recognize the power module. Hardware failure.
• Change to a different power module.
• Replace control module if changing power module does not work.

——

F109 Mismatch C-P
The control module was mounted to a different drive type power module.
• Set P053 [Reset To Defalts] to 3 “Power Reset”.

——

F110 Keypad Membrane
Keypad membrane failure / disconnected.
• Cycle power.
• Replace control module if fault cannot be cleared.

——

F111 Safety Hardware
Safety input enable hardware malfunction. One of the safety inputs is not enabled.
• Check safety input signals. If not using safety, verify and tighten jumper for I/O terminals S1, S2 and S+.
• Replace control module if fault cannot be cleared.

——

F114 uC Failure

Microprocessor failure.
• Cycle power.
• Replace control module if fault cannot be cleared.

——

F122 I/O Board Fail
Failure has been detected in the drive control and I/O section.
• Cycle power.
• Replace drive or control module if fault cannot be cleared.

——

F125 Flash Update Req
The firmware in the drive is corrupt, mismatched, or incompatible with the hardware.
• Perform a firmware flash update operation to attempt to load a valid set of firmware.

——

F126 NonRecoverablErr
A non-recoverable firmware or hardware error was detected. The drive was automatically stopped and reset.
• Clear fault or cycle power to the drive.
• Replace drive or control module if fault cannot be cleared.

——

F127 DSIFlashUpdatReq
A critical problem with the firmware was detected and the drive is running using backup firmware that only supports DSI communications.
• Perform a firmware flash update operation using DSI communications to attempt to load a valid set of firmware.

——

If you determine that your PowerFlex 525 drive needs service, or you’re just not sure, give us a call at 1-800-732-4695 to send your defective VFD in for repair. We have the experience necessary to get your defective PowerFlex 525 back in operation quickly with our quality repair service.

*There is a link to the troubleshooting section of the PowerFlex 525 manual below.

Понравилась статья? Поделить с друзьями:

А вот и еще интересные новости по теме:

  • Howtoplant ru система автополива инструкция по применению
  • Кровать лаки много мебели инструкция по сборке
  • Как ввести тампон с аппликатором инструкция
  • Прамотроник руководство по ремонту
  • Мануал для крайслер пацифика

  • 0 0 голоса
    Рейтинг статьи
    Подписаться
    Уведомить о
    guest

    0 комментариев
    Старые
    Новые Популярные
    Межтекстовые Отзывы
    Посмотреть все комментарии